local air conditioner PAC 2000 E
Error codes
The following error messages can be displayed on the segment display(14):
Error code Indication Fault Cause Remedy
F1
LED for cooling
operation(13)
lights up briefly
in a 3-second
cycle
Temperature
sensor for
ambient
temperature
The terminals at the temperature sensor for the
ambient temperature and at the mainboard are
loose or have no contact
Contact Trotec
Short circuit at the mainboard
Temperature sensor for the ambient
temperature defective
Mainboard defective
F2
LED for cooling
operation(13)
lights up briefly
twice in a
3-second cycle
Temperature
sensor for the
evaporator
The terminals at the temperature sensor for the
evaporator and at the mainboard are loose or
have no contact
Contact Trotec
Short circuit at the mainboard
Temperature sensor for the evaporator
defective
Mainboard defective
F4
LED for cooling
operation(13)
lights up briefly
four times in a
3-second cycle
Temperature
sensor for the
condenser
The terminals at the temperature sensor for the
condenser and at the mainboard are loose or
have no contact
Contact Trotec
Short circuit at the mainboard
Temperature sensor for the condenser
defective
Mainboard defective
E5
ON/OFF
button(17)
lights up briefly
five times in a
3-second cycle
Overvoltage
protection
The power supply is unstable and deviates from
the values on the nameplate by more than
10%
Connect the device to a power
supply conforming to the data on
the nameplate.
Power supply is too low or load is too high
Disconnect unnecessary loads in
the same grid from the power
supply.
Voltage at the mainboard is higher than the
overvoltage protection value
Contact Trotec
The inside of the device is heavily contaminated Contact Trotec
Air inlet or air outlet is blocked
Remove any foreign objects and
dirt from the air inlet and outlet.
Observe the minimum distances
specified in the technical data.
The fan does not run or runs too slowly Contact Trotec
Compressor malfunction: Temperature at the
housing is very high, compressor makes
unusual noises or refrigerant leaks
Disconnect the device from the
power supply and contact Trotec.
The system is blocked on the inside Contact Trotec
H8
Acoustic signal
8x in quick
succession
Condensate
overflow
protection
Too much condensate has accumulated in the
device
Discharge condensate, see
chapter Maintenance