CHANGING “DEFROST INTERVALS”:
May need to unlock control.
This can only be changed if defrost mode parameter “DFM” is set for “TIM”.
WHY: The defrost interval is the time duration between defrost cycles. The
defrost interval time starts when the cabinet is supplied power or after a manual
defrost.
STEP 1 - To see the set point, press and hold the Info button and the
Stand-by button at the same time.
NOTE: Depending on the version of control, one of three parameters will
appear: “ScL image 1a, “SPL image 1b, “MdL image 1c.
STEP 2 - Push the Up button until “dFt” appears. See image 2.
STEP 3 - Press and hold the Info button to see the defrost interval time.
See image 3
STEP 4 - While pressing and holding the Info button , press the
Up or Down button to change the defrost interval times (higher
the number the less frequent the cabinet will defrost).
STEP 5 - Once the defrost interval time has been changed, release the Info
button .
STEP 6 - Wait 30 seconds for the display to show temperature.
See image 4.
LAE Control
Manual Activation
Up Button
Info / Set Point
Button
Stand-By
Button
Manual Defrost /
Down Button
LAE ELECTRONIC TEMPERATURE CONTROLS