Appendix A. Back Pressure 
The quantity of air flowing through a supply diffuser or a return grille is reduced to some extent whenever 
a capture hood is placed over the flow opening. The amount of flow reduction will vary depending on the 
combined effects of the diffuser/grille resistance, the capture hood resistance, and the flow rate. 
 
The Electronic Balancing Tool and ProHood
™ capture hood features a built-in capability to make flow 
measurements which are compensated for the effects of the capture hood-induced back pressure. This is 
accomplished by taking two sequential flow measurements at a diffuser or grille, the first with the back 
pressure flap “OPEN” and the second with the flap “CLOSED”. The resulting Backpressure Compensated 
Flow displayed by the meter represents the air flow through the diffuser/grille in its original state, that is, 
without the presence of the capture hood. 
Verifying Flow Measurements 
It is always the recommended practice to verify the flow measurements obtained with a capture hood by 
performing appropriate
*
 multi-point, in-duct velocity traverses using a Pitot-static tube or a thermal 
anemometer. 
 
We recommend the use of the Log-linear method when traversing a round duct, and the Log-Tchebycheff 
method when traversing a rectangular duct. 
 
 
 
*
We recommend that you refer to the most up-to-date copy of the duct traverse specification you require from an approved 
regulatory or professional organization.