GENERAL2.1
Weight 12.0 kg including battery pack
& instantaneous adaptors
Dimensions 390 (L) x 240 (W)
x 210 (H) mm
Power Internal Battery Pack. DC
12V @ 250 mA
Case Material Corrosion resistant LM25
aluminium
Operating Temp. -10°C ~ +50°C
Adaptors 2.5” BSPM or BS Instantaneous
(4.0” BSPM for Flowmaster
400)
2.5” NST for USA and other
adaptors available on request
Colour Firemen Red & anodised
aluminium
Sensor Type Electromagnetic
Range 30 - 3,000 lpm
By changing the sensor control
pcb, range can be extended to
5,000 lpm
Resolution 50 ~ 750 l/min ± 15 l/min
750 l/min ~ ±2%
Standard Functions Flow reading
Totaliser reading
Casing Material Corrosion resistant ADC6-12
(JIS) aluminium (anodised)
Pressure rating 49 bar
Digital LCD display gauge
• 4 digits
• 17.6mm high digits
• Analog bar graph
• Internal backlighting
Type Strain Gauge
Range 0 ~ 25 bar, ±1%.
Digital LED display gauge
• 3 digits (16.0 mm high digits)
• Bar
or PSI readout selectable
• Internal data logger
• 64Kb memory capacity. Record 6 hours of data at one
second interval
• Records ow rate and pressure
SPECIFICATION
2
FLOWMETER2.2
PRESSURE TRANSDUCER AND DISPLAY2.3
DATA LOGGER2.4
Battery Type Valve regulated rechargeable
lead acid
Rated Capacity 2.4 Ah (10 hours continuous
operation)
Recharging Mains operated recharger is
supplied
BATTERY PACK2.5
• Real time clock and date/time stamp added to each
recorded event
• USB connection to PC for settings and for recorded
data transfer
• Automatic trigger of logger by ow event or manual
operation using push button
• FMS software supplied for management of logged les
and report generation
• Each log le is identied by its recorded date and
recorded time
• File name can be edited in software
• Graph of logged data is automatically produced.
Auto-scaling ensures data ts into the frame
• Text notes can be added to the graph
• Graph can be printed directly from FMS software or
stored as a .BMP le for inclusion in MS Word or MS
Excel documents
• USB cable is supplied
SOFTWARE2.6
MANUALS2.7
The following manuals are provided on a CD supplied
with the Flowmaster:
• Operation and Maintenance Manual
• Software Manual
• You Tube videos demonstrating how to use the
Flowmaster 250DL
• You Tube videos demonstrating how to use the ow
monitoring software supplied with the Flowmaster
250DL
Please go to www.tsi.ie for manual updates.
Version 2.0 (February 2012) TSI Flowmeters Ltd.6