The ROOM MODE item selects the room pressure direction. 
This item enables all related alarms for pressure direction 
selected. Selecting key switch enables a remote TSI key 
switch, which determines pressure direction. 
 
KEY SWITCH, 
NEGATIVE, 
POSITIVE, NO 
ISOLATION 
The DISPLAY AVG item selects the display’s averaging 
period. The display averaging period is the length of  time the 
room pressure has been averaged before being displayed. 
The DISPLAY AVG item value may be set between 0.75 and 
40 seconds. The higher the averaging value, the more stable 
the display. 
 
0.75, 1, 2, 3, 5, 10, 20, 
or 40 seconds 
 
The UNITS item selects the unit of measure that the controller 
displays all values (except calibration span). These units 
display for all menu items set points, alarms, flows, etc. 
 
FT/MIN, m/s, "H
2
O 
Pa, mm H
2
O 
 
DUCT AREA 
 
Premium 
models only 
The DUCT AREA item is used to input the duct size. The duct 
size is needed to compute the flow in/out of the room. This 
item requires a TSI flow station to be mounted in the duct. 
 
When a duct area is programmed, the display will 
automatically scroll the actual flow as part of the display 
sequence. If a zero value is entered, the flow value will not 
scroll on the display. 
 
If the PresSura controller displays English units, area must be 
entered in square feet. If metric units are displayed area must 
be entered in square meters. 
 
0 to 10 square feet 
(0 to 0.9500 square 
meters) 
 
The PresSura 
controller does not 
compute area. The 
area must be first 
calculated and then 
entered into the unit. 
ROOM 
VOLUME  
 
Premium 
models only 
The ROOM VOLUME item is used to input the volume of the 
room. The room volume is required to calculate air changes per 
hour.  
 
Entering a value for the volume will add the air changes per 
hour value to the display’s scrolling sequence. If a zero value is 
entered the air changes per hour will not scroll on the display.  
 
If the PresSura controller displays English units, area must be 
entered in cubic feet. If metric units are displayed area must be 
entered in cubic meters. 
0 to 20,000 cubic feet  
(0 to 550 cubic  
meters) 
 
The PresSura 
controller does not 
compute volume. The 
volume must be first 
calculated and then 
entered into the unit.