Pressure sensor must have DIP switch correctly set for 
proper sign display. Verify DIP switch 4 is ON when 
sensor is mounted in isolation room (controlled space), 
and OFF when mounted in reference space (see Figure 
9). 
 
Primary pressure sensor must have address of 1. 
Second sensor must have address of 2. Check pressure 
sensor DIP switches 5 & 6 and verify address is correct 
(7 to 12 must be OFF). 
 
Verify wiring is correct between key switch and DIM.  
 
Go into CONFIGURE menu, ROOM MODE item. Verify 
ROOM MODE is in key switch position. 
 
Verify ROOM MODE is in key switch position. Go into 
DIAGNOSTICS menu, KEY INPUT item. Display should 
read negative in negative position, positive in positive 
position, and no isolation in neutral position. If display 
changes correctly, switch and switch input is good. If 
display does not change: 
 
Disconnect key switch wires from DIM pins 11 and 12. 
Measure the resistance of the switch: 
 Negative position should be open (infinite). 
 Neutral position should read approximately 273 K 
Ohms. 
 Positive position should be closed (short). 
 
If room mode is correct and resistance check is good, 
DIM key input is probably defective. Replace DIM.