Press TEST key. The individual alarm set points will 
display. If all alarm set points are zero, alarm relay is not 
active, so relay will not be required to change state.  
 
Check the wiring from PresSura controller relay's output 
to the device that is connected to the relays. 
 
The relay contacts only work for primary pressure 
alarms. The relays do not activate when a second 
sensor or flow alarm condition occurs (DIM light and 
audible do activate). This is because the primary 
pressure alarms are the most important or have the 
highest priority.  
 
Disconnect the wiring from relay contact pins 13 and 14 
for low alarm relay and pins 25 and 26 for high alarm 
relay. Go into DIAGNOSTICS menu, LOW ALM REL or 
HIGH ALM REL. Connect an ohmmeter to relay 
terminals to verify contact open and closes. Press 
the/ key to manually trip the relay. If relay responds 
(contact opens and closes), the device connected is 
incompatible or defective. If relay doesn’t respond, relay 
is defective (may be caused by incompatible device). 
Replace DIM. 
 
Check supply and exhaust flow for stability. Verify 
reference pressure is not fluctuating. 
 
Check location of supply air diffusers and exhaust 
grilles. They should be as far from pressure sensor as is 
realistic, 6 feet preferred, 2½ feet minimum. Supply 
diffuser terminal throw velocity must be less than 10 
ft/min at the sensor. Relocate supply or exhaust as 
needed. 
 
This symptom occurs when multiple devices are being 
ran off one transformer. Each system must be powered 
by its own transformer or have an isolation transformer 
installed. 
 
NOTE:  Unit may hunt due to speed of system and may 
not be tied to ground loop problem.