20 21
7.4 Filling a Tua Fuel Station
1. Fillingshouldbeperformedonlyunderconstantsupervisionofanauthorisedperson.
2. Thistankcanonlybelledbyatankerequippedwitha2”femaleBSPcoupling.
3. On3500/6000/10000/15000modelsbeforellingthetankwithdiesel,please
checkthelevelofthetankandmakenoteofthetanklevelbeforellingandensurethe
high-levelalarmindicatorfunctionscorrectly.
4. Fittankerdeliveryhoseto2”BSPllcouplingontank.
5. Engagetankerpumpandbegintoll.Stopllingwhendesiredamounthasbeen
dispensedintotank,orwhenhigh-levelalarmsounds.
6. Duringthetankerllalwaysobservetanklevelgaugethroughoutthedurationofthe
llingprocess.Thetankerdrivermustobservethetankbeinglledatalltimesduringthis
process.
7. Oncecompletedisconnectdeliveryhosefromtankcoupling.
7.5 Dispensing diesel into vehicle
1. Resettheowmetertotalizerto0.
2. Activatepumpusingoneofthefollowing:rockerswitch/keyswitch/auto-
operationalnozzleholster/batterycableclips.
3. Removenozzlefromnozzleholsterandinsertthenozzlecompletelyintothediesel
tankllerneck.
4. Pulltriggeronthenozzletoallowdieseltoowintothevehicledieseltank.
5. Atthistimetheowmetercounterwillstartrecordingtheow,continuerefuelinguntil
thedesiredamountisreachedorwhenthevehicledieseltankisfull.
6. Whenthefueltankisfullthenozzlewillautomaticallyswitcho.
7. Releasethetriggerofthenozzleandreplacebackintotheholster.
8. Deactivatepumpwithrockerswitch/keyswitch/autooperationalnozzleholster/
removalofbatterycableclips.
7. OPERATION OF THE SYSTEM
7.6 Equipment components
1. FMS gauge level (3500 litres models and above)
TheFuelLevelMonitoringSystemisa240vcombineddigitaltanklevelindicatorandbund
andhigh-levelalarmthatisdesignedtoprovidebothvisualandaudiblealarmswhenevera
predeterminedlevelinastoragetankisreached.TheFMSgivesacontentreadoutinboth
litresandapercentage.
a. Full alarm
Activationofthisalarmindicatesthatthetankisfull.Thisalarmisshownthroughvisual
LED’sandaudiblesiren.Note:Thisaudibleandvisualalarmwillremaintriggeredfora
shortperiodoftimeafteritsounds.Theaudiblecanbemutedusingthemutebuttononthe
keypad.THEPUMPWILLCONTINUETODISPENSEINTHISALARMMODE.
b. High level alarm
Activationofthisalarmindicatesthetankhasreachedahighcapacityandcloseattention
mustbepaidtothedieselinsidethetank.ThisalarmisshownthroughvisualLED’sand
audiblesiren.Note:Thisaudibleandvisualalarmwillremaintriggeredforashortperiodof
timeafteritsounds.Theaudiblecanbemutedusingthemutebuttononthekeypad.THE
PUMPWILLCONTINUETODISPENSEINTHISALARMMODE.
7. OPERATION OF THE SYSTEM