F13:
Number of post cleaning cycles after stopping the fan.
Possible values: 0199 step 1.
Default = 01.
F14:
Post cleaning mode pause time between solenoid valves (fan off).
Possible values: 001” – 999step 1.
Default = 10.
F15:
Maintenance frequency expressed in tens of hours (e.g.: 1=10h, 10=100h).
Possible values: 001999 step 1.
Default = 100 (=1000h).
F16:
Maintenance deadline alarm enable.
Possible values: 0 (disabled) 1 (enabled).
Default = 0 (disabled).
F17:
Maintenance hour counter reset.
Possible values: 0 (disabled) 1 (reset).
Default = 0 (disabled).
The maintenance hour counter will be reset and the F17 parameter will be set back to 0 by
setting F17 to 1.
F18:
Precoating function enabling.
Possible values: 0 (disabled) 1 (enabled).
Default = 0 (disabled).
F19:
dP threshold for precoating function.
Possible values: 0.00 kPa 3.99 kPa step 0.01.
Default = 2.00 kPa.
F20:
Enabling Minimum dP Alarm function if detected for longer than 60 seconds.
Possible values: 0 (disabled) - 1 (enabled).
Default = 0 (disabled).
F21:
Min dP Alarm Threshold (Broken Sleeve/Cartridge)
Possible values: 0.00 kPa 3.99 kPa step 0.01.
Default = 0.20 kPa.
F22:
Selection of minutes or hours for Forced Cleaning Cycle. (Only if the operating mode
F01 = 2)
Default = Minutes (0 =minutes, 1 =hours).
F23:
Setting time interval for Forced Cleaning Cycle in relation to the choice of F22.
Setting values: 1 - 999 step 1.
Default = 240 (240 minutes).
F24:
Exclusion of valve in Short Circuit.
The default setting is 0, the valve in Short Circuit is tested at each cycle.
If set to 1, when a valve is in short circuit is excluded from the cycle and is not rechecked.