After Set is selected, a message will appear asking for
confirmation of the action to send the data to the device,
as follows:
TEST RI TERMINAL
TEST RI TERMINAL tests the remote indicator output.
Selecting this menu option displays either PASS or FAIL.
TEST L2 TERMINAL
TEST L2 TERMINAL tests the functional base interface
output. Selecting this menu option displays either PASS or
FAIL.
BACKLIGHT
This controls the display backlight. If On is selected, the
display is illuminated for 6 seconds on each button press.
The display can also be temporarily illuminated by pressing
any two buttons simultaneously at any time.
Note: Use of the backlight will reduce battery life.
AUTO POWER OFF
AUTO POWER OFF is designed to save battery life. If there
have been no button presses during a preset time period, the
Service Tool automatically turns itself off. This menu option
allows the preset time period to be increased or decreased.
The timer is set by the user, after which the Service Tool turns
itself off. The preset time period may be increased (or
decreased) firstly in 1 minute steps, then in 5 minute steps up
to 60 minutes maximum.
Use Dn and Up to decrease or increase the
timer period
Choose Set at the required level and then
press Menu to return to the main menu
STORE SETTINGS
The following settings may be changed during use and this
option enables the current values to be stored. The stored
values are recalled when the unit is next powered up. The
settings saved are: Auto Power-off time and Customer Code.
Menu - returns to the menu option
Def - returns to default settings
ClU - clears list of previously used addresses
Sto - select to save changed settings
Any settings which are changed and not stored will be lost
when the Service Tool powers down.
Note: Used addresses are stored automatically.
CUSTOMER CODE
CAUTION:
THIS MENU OPTION CHANGES THE
CUSTOMER CODE OF THE SERVICE TOOL AND
SHOULD ONLY BE USED FOR DE-BUGGING
PURPOSES. IT SHOULD BE SET TO 254
NORMALLY.
Note:
1) Communication is only possible if the same
customer code is present in the addressable
device and the service tool.
2) The addressable device is manufactured with a
default code of 254. This is set in the device and
cannot be changed.