30
override the controller’s temperature control and force its output switch off or on. As a TEMPBUS™ 
temperature source, either controller can control its output switch using the 
TEMPBUS™ temper-
ature rather than temperatures from 
TS 1 or TS 2.
Setting: NOT USED, TEMPBUS (V3.11+), INHIBIT or FORCE ON (V3.11+)
Procedure: If the 
EXTERNAL INPUT is not being used by either point, select NOT USED. If either 
point requires a 
TEMPBUS™ temperature signal, select TEMPBUS™ and set the point TS CONTROL 
MODE
 to a mode using the EXTERNAL INPUT (see section 3.5.12 on page 24). For TEMPBUS™ 
operation description see section 5.4 on page 53. 
If a remote dry contact closure should force either point’s output switch off, select 
INHIBIT. If a 
remote dry contact closure should force either point’s output switch on, select FORCE ON. 
If the 
EXTERNAL INPUT is set to INHIBIT or FORCE ON, the point’s OVERRIDE SOURCE (for V3.11+) 
must be set to 
EXT. INPUT or its INHIBIT CONTROL (for V3.00) must be enabled.
Notes:
• When used with the 
INHIBIT/FORCE ON feature, a contact closure sensed by the EXTERNAL 
INPUT
 will initiate the INHIBIT/FORCE ON mode. An open input will cause the controller to 
revert to normal temperature control operation. One possible use of the 
INHIBIT feature is to 
use an external device (such as a flow meter) to provide a contact closure if there is flow in a 
line. As long as the line has adequate flow, the heating will be off (
INHIBITed from operating). 
See Appendix C on page 68 for typical connection diagrams when using this input.
•
EXTERNAL INPUT must be set to INHIBIT or FORCE ON before OVERRIDE SOURCE (for V3.11+) 
can be set to 
EXT. INPUT; or INHIBIT CONTROL (for V3.00) can be edited. For V3.11 and up, set-
ting 
EXTERNAL INPUT to NOT USED or TEMPBUS™ will automatically set OVERRIDE SOURCE to 
REMOTE.
3.6.4  EXTERNAL OUTPUT PORT
Purpose: The 
EXTERNAL OUTPUT port can be programmed to allow Point A to function as a “mas-
ter” 920 
HTC to control up to 25 “slave” 920 HTC units. A “master” can either force its “slaves” to 
override their temperature control and force their output switch off (INHIBIT), or it can send its 
control temperature to its “slaves” so they can do their own temperature control using this tem-
perature (
TEMPBUS™). 
 An INHIBIT “master” may be useful when a number of “slave” controllers use their own RTDs, 
but are to be turned off based on the ambient temperature. This will allow disabling of the 
“slave” controllers during the summer months, during a maintenance shutdown, etc.
A 
TEMPBUS™ “master” may be useful when a number of “slave” controllers do not have their 
own temperature sensors and are set to control the ambient temperature.
Setting: 
NOT USED, TEMPBUS (V3.11+) or INHIBIT
Procedure: Select NOT USED if Point A is not a “master” controlling the EXTERNAL OUTPUT port. 
Select 
INHIBIT if Point A will be controlling the EXTERNAL OUTPUT port as an INHIBIT “master.” 
Select 
TEMPBUS™ if Point A will be sending its control temperature out the EXTERNAL OUTPUT 
port. For 
TEMPBUS™ operation description see section 5.4 on page 53.
Notes:
• The “master” and “slave” controllers must be installed in the same enclosure. The 
EXTERNAL 
OUTPUT PORT
 signal is not intended to be connected over extended distances or between 
enclosures.
•If 
EXTERNAL OUTPUT is set to INHIBIT, then the DEADBAND parameter for Point A will be used 
to define the operation of the 
EXTERNAL OUTPUT port, even though the SWITCH CONTROL 
MODE
 for Point A may not be set for DEADBAND operation. See section 3.5.5 on page 22 for 
additional details regarding the 
DEADBAND mode.
• If the 
EXTERNAL INPUT PORT input is not being used, Point B may be configured as a “slave” 
for a controller with its Point A configured as a “master.”