EasyManua.ls Logo

Tyco DigiTrace 920 Series - Page 43

Tyco DigiTrace 920 Series
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
43
Setting: HTCBUS or MODBUS ASCII (V3.11+) or MODBUS RTU (V3.11+)
Procedure: Select the HTCBUS™ protocol when communicating with existing Tyco Thermal Con-
trols Heat Trace Control products, including the Model 780/GCC-9000 Group Communications
Controller.
If you are communicating directly with the controller using a different device, select the
MODBUS
protocol. For a detailed description of the controller’s
MODBUS mapping, please refer to the sep-
arate DigiTrace 920 Series Heat Trace Controller—Modbus Protocol Interface Mapping docu-
ment (Tyco Thermal Controls reference H57366 ).
3.9.2 HTCBUS™ ADDRESS
Purpose: Defines the communications address to be used by the controller when using the
HTC-
BUS™
protocol to communicate with a Model 780/GCC-9000. When in the Point A configuration
menu, this sets the Point A
HTCBUS™ ADDRESS; when in the Point B configuration menu, this
sets the Point B
HTCBUS™ ADDRESS. Either may be set independently of the other.
Range: 1 to 16,777,215
Procedure: Set the communications address as desired. This must be an address unique to the
entire communications network to avoid messaging conflicts. The
HTCBUS™ protocol must be
selected in order to set the
HTCBUS™ ADDRESS.
Note: A unique HTCBUS communications address is always assigned by Tyco Thermal Controls
and identified by the label on the front of the 920 control module (see Figure 3.1). Use the preas-
signed address whenever possible to minimize the chances of an address being duplicated in the
user’s system.
3.9.3 MODBUS ADDRESS (V3.11 AND UP)
Purpose: The
MODBUS™ ADDRESS, along with the MODBUS™ SUB ADDRESS, defines the commu-
nications address to be used by the controller when using either
MODBUS™ protocol to commu-
nicate with a
MODBUS™ compatible device. When in the Point A configuration menu, this sets the
Point A
MODBUS™ ADDRESS; when in the Point B configuration menu, this sets the Point B MOD-
BUS™ ADDRESS
. Either may be set independently of the other.
Range: 1 to 247
Procedure: Set the communications address as desired. Together with the
MODBUS™ SUB
ADDRESS
, this combination must be unique to the entire communications network to avoid mes-
saging conflicts. Either
MODBUS™ protocol must be selected in order to set the MODBUS™
ADDRESS
.
3.9.4 MODBUS SUB ADDRESS (V3.11 AND UP)
Purpose: The
MODBUS™ SUB ADDRESS, along with the MODBUS™ ADDRESS, defines the commu-
nications address to be used by the controller when using either
MODBUS™ protocol to commu-
nicate with a
MODBUS™ compatible device. When in the Point A configuration menu, this sets the
Point A
MODBUS™ SUB ADDRESS; when in the Point B configuration menu, this sets the Point B
MODBUS™ SUB ADDRESS. Either may be set independently of the other.
Range: 0 to 31
Procedure: Set the communications sub address as desired. Together with the MODBUS™
ADDRESS
, this combination must be unique to the entire communications network to avoid mes-
saging conflicts. Either
MODBUS™ protocol must be selected in order to set the MODBUS™ SUB
ADDRESS
.
Note: Since a 920 HTC does not use all 65,535 data addresses available for each MODBUS™
ADDRESS
, this data address range is subdivided to allow up to 32 HTCs to share the same MOD-
BUS™ ADDRESS
. This increases the number of HTCs allowed on a single MODBUS™ port from 247
to 7,904 (=247 x 32). This requires that any
HTC sharing the same MODBUS™ ADDRESS as
another
HTC must have its own unique MODBUS™ SUB ADDRESS.

Table of Contents

Related product manuals