Current Turns Ratio 1.00 to 1
Autocycle Enable
Autocycle Interval 8
Autocycle Units Hours
Inhibit Ctl Disable
Load Shedding Disable
Configuration Mode Main Menu
Parameter Factory User
Control Setpoint 68°F (20°C)
TS Alarms Configuration Sub-Menu
Parameter Factory User
TS 1 Fail Enable
Lo TS 1 Alarm Enable
Lo TS 1 14°F (–10°C)
Hi TS 1 Alarm Enable
Hi TS 1 212°F (100°C)
TS 2 Fail Disable
Lo TS 2 Alarm Disable
Lo TS 2
Hi TS 2 Alarm Disable
Hi TS 2
Latch TS Alarms Yes
TS CTL Fail Alarm Enable
Point Setup Sub-Menu (Continued)