22.6 Panel Configuration Design Chart
Table 1 – Motherboard DIL Switch Configuration Design/Record
Switch Function Position
Actual
Setting
1-1
Fire Protection relays operate for a fire condition on any zone.
Off
Fire Protection relays operate for a fire condition on any latching fire zone.
On
1-2
Silence and reset available as normal.
Off
Prevents alarm silence & reset for a period of 3 minutes after a fire alarm
condition occurs. [Does not apply to Muster Alarm]
On
1-3
T1216W-C use onlyleave in OFF position.
1-4
Configuration mode disabled.
Off
N/A
Zones can be configured to non-latch mode via the Engineer’s Select
feature.
On
Table 2
1-5
Configuration mode disabled.
Off
N/A
Zones can be configured to Intrinsically Safe monitoring mode.
On
Table 2
1-6
Configuration mode disabled.
Off
N/A
Configure zones as Machinery Space Zones see section 17.4.
On
Table 2
1-7
Not functional.
1-8
Configuration mode disabled.
Off
N/A
Configure delayed outputs via the Engineer’s Select feature.
On
Table 3
1-9
Not functional.
1-10
Sounders operate on any fire condition including Manual Fire Alarm/Muster.
Off
Sounders operate only when the panel is in the Manual Fire Alarm/Muster
condition.
On
2-1
Panel can be reset while sounders are active.
Off
Panel can be reset only after sounders are silenced.
On
2-2
Continuous Alarm Sounder mode.
Off
Pulsed Alarm Sounder mode.
On
2-3
In Crew Mode, after Sounders have been silenced before delay ends:
A new detector fire condition operates all sounders & O/Ps without delay.
Off
In Crew Mode, after Sounders have been silenced before delay ends:
A new detector fire condition restarts 2-minute delay.
On
2-4
Not functional.
2-5
Not functional.
2-6
DIL SW 2-7 OFF: General Alarm Sounder Mode.
DIL SW 2-7 ON: Crew Alert Modesee section 17.10.
Off
Zonal Sounder Mode (see also 2-7)
On
2-7
DIL SW 2-6 OFF: No Effect.
DIL SW 2-6 ON: Zonal sounders for zones in fire operate as per switch 2-2
setting all other zones are silent.
Off
DIL SW 2-6 OFF: Crew Alert Mode.
DIL SW 2-6 ON: Zonal sounders operate as per switch 2-2 setting - all
other sounders pulse.
On
2-8
Sounders operate in response to zone test.
Off
Sounders do not respond to a zone test.
On
2-9
Buzzer enabled.
Off
Buzzer disabled.
On
2-10
Non-latched fault indication.
Off
Latched fault indication.
On