22.6  Panel Configuration Design Chart 
Table 1 – Motherboard DIL Switch Configuration Design/Record 
Switch  Function  Position 
1-1 
Fire Protection relays operate for a fire condition on any zone. 
 
Fire Protection relays operate for a fire condition on any latching fire zone. 
 
1-2 
Silence and reset available as normal. 
 
Prevents alarm silence & reset for a period of 3 minutes after a fire alarm 
condition occurs. [Does not apply to Muster Alarm] 
On  
 
T1216W-C use only – leave in OFF position. 
1-4 
Configuration mode disabled. 
N/A 
Zones can be configured to non-latch mode via the Engineer’s Select 
feature. 
Table 2 
1-5 
Configuration mode disabled. 
Zones can be configured to Intrinsically Safe monitoring mode. 
Table 2 
1-6 
Configuration mode disabled. 
Configure zones as Machinery Space Zones see section 17.4. 
Table 2 
1-8 
Configuration mode disabled. 
Configure delayed outputs via the Engineer’s Select feature. 
1-10 
Sounders operate on any fire condition including Manual Fire Alarm/Muster. 
 
Sounders operate only when the panel is in the Manual Fire Alarm/Muster 
condition. 
 
2-1 
Panel can be reset while sounders are active. 
 
Panel can be reset only after sounders are silenced. 
 
2-2 
Continuous Alarm Sounder mode. 
 
Pulsed Alarm Sounder mode. 
 
2-3 
In Crew Mode, after Sounders have been silenced before delay ends: 
A new detector fire condition operates all sounders & O/Ps without delay. 
 
In Crew Mode, after Sounders have been silenced before delay ends: 
A new detector fire condition restarts 2-minute delay. 
 
2-6 
DIL SW 2-7 OFF: General Alarm Sounder Mode. 
DIL SW 2-7 ON: Crew Alert Mode – see section 17.10. 
Off 
 
Zonal Sounder Mode (see also 2-7) 
 
2-7 
DIL SW 2-6 OFF: No Effect. 
DIL SW 2-6 ON: Zonal sounders for zones in fire operate as per switch 2-2 
setting – all other zones are silent. 
Off 
 
DIL SW 2-6 OFF: Crew Alert Mode. 
DIL SW 2-6 ON: Zonal sounders operate as per switch 2-2 setting - all 
On  
 
2-8 
Sounders operate in response to zone test. 
 
Sounders do not respond to a zone test. 
 
2-9 
 
 
2-10 
Non-latched fault indication. 
 
Latched fault indication.