Instructions for the installer
00361435
00360360
00360351
00360352
00360353
00360355
00360353 00360354
00360351
00361435
00360360
00360351
00360355
00360352
00360353
00360356
KIT5790C
Example N.1
Intake of primary air from the perimeter wall and flue dischar-
ge from the roof.
17,4 m -
0,8 m -
1,2 m -
2,8 m =
12,6 m
Example N.2
Intake of primary air and flue discharge from two external pe-
rimeter walls.
It is not permitted to position the two terminals on opposite
walls.
L max =
2 Curve with wide radius
1 horizontal suction terminal
1 horizontal evacuation terminal
17,4 m -
1,6 m -
1,2 m -
2,0 m =
12,6 m
L max =
1 Curve with wide radius
1 horizontal suction terminal
1 Vertical evacuation duct
With this configuration there are still 12,6 m
available to be shared between the suction
and evacuation ducts.
With this configuration there are still 12,6 m
available to be shared between the suction
and evacuation ducts.