26
3.11 - MEASUREMENT OF COMBUSTION EFFICIENCY DURING INSTALLATION
ATTENTION!
Function reserved for Authorised
Assistance Centres only.
3.11.1- ACTIVATION OF THE CALIBRATION FUNCTION
1 ACTIVATION
Press the key (D) for at least 5 seconds, until
SErvice appears.
All the symbols ash on the display.
2 MAXIMUM OUTPUT
When the high ame symbol is xed on the display
and it alternates between SP and the ow temper-
ature, the boiler operates at maximum output.
Perform combustion analyses.
4 DISABLING
The “calibration” function stays active for 15 min-
utes.
To disable the CALIBRATION function before the
time elapses press the key (D) for 5 seconds, until
SErvice
disappears.
3 MINIMUM OUTPUT
Press the key (C-), when the low ame symbol is
xed on the display.
and it alternates between SP and the ow tem-
perature, the boiler operates at minimum output.
Perform combustion analyses.
The user is NOT authorised to activate the func-
tion described below.