8
ATTENTION (*) see general warn-
ings 1.1
The heating only models are NOT
suitable for the production of water
for human consumption according
to Ministerial Decree D.M. 174/2004.
ATTENTION!
ANY DAMAGE TO THE BOILER
CAUSED BY THE FORMATION OF
FOULING OR BY CORROSIVE WATER
WILL NOT BE COVERED BY THE
WARRANTY.
1.8 - BOILER ANTIFREEZE
PROTECTION (*)
Make sure that E is lit up
on the display
(
), select the mode
using B / C.
(*) The Antifreeze protection is always active.
Even by disabling the heating and domestic hot
water services,
in this mode (
)only the antifreeze function is
active.
1.7 - WATER TREATMENT
The treatment of the supply water
allows to prevent inconveniences
and maintain the functionality and
e󰀩ciency of the generator over time.
The ideal water pH in heating systems
must be within:
To minimise corrosion, it is crucial to
use a corrosion inhibitor; in order for
it to work properly, the metal surfac-
es must be clean.
(see system protection ACCESSO-
RIES sect. in domestic price list)
This protection can intervene only if
the electricity and gas supplies are
connected.
If one of the two is not available and
upon reset 11 (SR) a temperature of < 2
°C is detected, the appliance will behave
as described in tab. pos 2.
The heating system can be protected
e󰀨ectively from frost by using antifreeze
products with inhibitor for heating
systems (specic for multidmetal).
Do not use car engine antifreeze
products as they could damage the
water gaskets.
VALUE MIN MAX
PH 6.5 8
Hardness [°fr] 9 15
NOTE!
Further details in the section
‘Technical Information’’ on the
boiler
page of the www.unicalag.it website
P
O
S
ANTIFREEZE FUNCTION
Power supplies 11 - SR (*) Status
function
antifreeze
Actions
Electric Gas
1
ON ON < 6 °C ON - Burner and Pump ON until T > 14°C
ON ON < 2 °C ON Only when both the power supplies are ON:
- Burner and Pump OFF until T > 5°C
- When T > 5°C then Burner and Pump
ON until T > 14°C.
2
ON OFF < 7 °C OFF - Pump ON till T > 10°C
OFF ON OFF - Burner and Pump OFF
OFF OFF OFF - Burner and Pump OFF
(*) Sensor 11 par. 2.2