28
KON
e
R 35 - KON
e
C 35
Type of
Gas
Eective
Ouput
[kW]
Heating
Thermal
[kW]
Capacity
Supply
Press.
[mbar]
Fan
speed
[rpm]
Collector
diaphragm
[Ø/n.
holes]
CO
2
levels
[%]
Con-
sumption
Con-
sumption
Start-up
power
IG [%]
min max min max min max
Gas nat. (G20) 4,3 - 32,0 4,4 - 33,0 20 - - - 9,3 9,3 0,47 m³/h 3,49 m³/h -
Gas nat. (G25) 4,3 - 32,0 4,4 - 33,0 25 - - - 9,3 9,3 0,54 m³/h 4,06 m³/h -
Propano (G31) 5,5 - 32,0 5,6 - 33,0 37 - - - 10,5 10,5 0,43 kg/h 2,56 kg/h -
A.P. (G230) 4,3 - 32,0 4,4 - 33,0 20 - - - 9,6 9,0 0,34 m³/h 2,57 m³/h
(*) ± 0,2 Acceptable range for G20 / G25 (+) ± 0,2 Acceptable range for G31 / G230
KON
e
R 28 - KON
e
C 28
Type of
Gas
Eective
Ouput
[kW]
Heating
Thermal
[kW]
Capacity
Sup-
ply
Press.
[mbar]
Fan
speed
[rpm]
Collector
diaphragm
[Ø/n.
holes]
CO
2
levels
[%]
Con-
sumption
Con-
sumption
Start-up
power
IG [%]
min max min max min max
Gas nat. (G20) 4,3 - 27,2 4,4 - 28,0 20 - - - 9,3 9,3 0,47 m³/h 2,96 m³/h -
Gas nat. (G25) 4,3 - 27,2 4,4 - 28,0 25 - - - 9,3 9,3 0,54 m³/h 4,06 m³/h -
Propano (G31) 5,5 - 27,2 5,6 - 28,0 37 - - - 10,5 10,5 0,43 kg/h 2,17 kg/h -
A.P. (G230) 4,3 - 27,2 4,4 - 28,0 20 - - - 9,6 9,0 0,34 m³/h 2,18 m³/h
(*) ± 0,2 Acceptable range for G20 / G25 (+) ± 0,2 R Acceptable range for G31 / G230
If the CO
2
value detected is beyond the recommended range, check the integrity of the electrode.
If needed, replace the electrode.
If the problem persists one can use the function described below.
Note: for operation with Propane air (A.P.) follow the procedure to adapt to another gas at Par.
4.3 setting the parameter for operation with Propane (1) and follow the GAC Automatic Cali-
bration procedure in Par. 4.3.1.
INCONVENIENCES SOLUTIONS
KON
e
18 - 24 - 28 - 35
Flame noisy
in cold ignition
Act on parameter ‘’IG’’ using the RCh section ‘’TECHNICAL MENU’’ TSP
parameters increasing the value by 5 ÷ 10 % max
KON
e
18 - 24 KON
e
28 - 35
Flame noisy in
steady-state conditions
increase the CO
2
value
- max value for methane gas = 9.4 %
(min value > 9.0 %)
- max value for propane = 10.7 %
(min value > 10.3 %)
- max value for A.P. = 9,2 %
(min value > 9.4 %)
increase the CO
2
value
- max value for methane gas = 9.5 %
(min value > 9.1 %)
- max value for propane = 10.7 %
(min value > 10.3 %)
- max value for A.P. = 9,2 %
(min value > 9.4 %)
Flame noisy in
modulation