Page 46
POWERING TECHNOLOGY
Manual No. MS0027-MAN rev. 4
guardian_access_3u_ms27-man-rev4-0817.indd
Fault Possible Cause Suggestion/Solution
Module Failure
Faulty module.
AC OFF on a single rectier (if more
than one rectier is installed).
Rectier current sharing fault.
Low DC output voltage, overvoltage
shutdown, module fan failure, module
is overheated.
Check if module sends alarm ag.
Verify the AC voltage to the failed
module.
Re-insert the faulty module, wait for
30 seconds
Replace the faulty module.
Urgent Module
Failure
More than one rectier is reporting
Module failure.
See Module failure alarm.
High Load
Faulty module .
Rectier load current exceeds the set
High load limit [%].
Compare the load current with
installed rectier capacity.
Add a rectier or reduce load.
Verify the High load limit setting.
Replace the faulty module.
Overvoltage
Shutdown
Faulty module Re-insert the module, wait for 5
minutes.
Replace the faulty module.
Load/Battery
Disconnection
System voltage drops below the set
limit.
System shutdown.
Check the battery condition.
Check the AC mains connection.
Check the input breaker.
Check the rectier modules.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Unipower Guardian Access 3U and is the answer not in the manual?

Unipower Guardian Access 3U Specifications

General IconGeneral
BrandUnipower
ModelGuardian Access 3U
CategoryPower Supply
LanguageEnglish

Related product manuals