Technical Specifications
Power supply
Input voltage
24VDC
Permissible range
20.4VDC to 28.8VDC with less than 10% ripple
Current Consumption
See Note 1
JZ20-UA24
JZ20-J-UA24
JZ20-UN20
JZ20-J-UN20
Max. current consumption
230mA@24VDC
185mA@24VDC
Notes:
1. To calculate the actual power consumption, subtract the current for each unused
element from the maximum current consumption value according to the values below:
Per relay output
LCD backlight
Per Analog Output,
(JZ20-UA24/
JZ20-J-UA24 only)
Max. current per element
5.5mA@24VDC
35mA@24VDC
23mA
Digital Inputs
Number of inputs
11 (Two groups) see Note 2 & 3
Input type
pnp (source) or npn (sink)
Galvanic isolation
None
Nominal input voltage
24VDC
Input voltage
pnp (source)
0-5VDC for Logic ‘0’
17-28.8VDC for Logic ‘1’
npn (sink)
17-28.8VDC for Logic ‘0’
0-5VDC for Logic ‘1’
I0-I8
I9-I10
Input current
3.7mA@24VDC
1.2mA@24VDC
Response time
10mSec typical
20mSec typical
Input cable length
Up to 100 meters, unshielded
High speed inputs
Specifications below apply when wired as H.S.C. See Note 4.
Resolution
16-bit
Frequency
5kHz maximum
Minimum pulse width
80μs
Notes:
2. JZ20-UN20/ JZ20-J-UN20 and JZ20-UA24/ JZ20-J-UA24 comprise I0-I8; these inputs
are arranged in a single group. Via wiring, the entire group may be set to either pnp or
npn.
3. JZ20-UN20/ JZ20-J-UN20 and JZ20-UA24/ JZ20-J-UA24 comprise I9 & I10. These
may be wired as either digital or analog inputs, as shown in the
JZ20-UA24/ JZ20-J-UA24 and JZ20-UN20/ JZ20-J-UN20 Installation guides.
I9 & I10 may be wired as npn, pnp, or 0-10V analog inputs. one input may be
wired as pnp, while the other is wired as analog. If one input is wired as npn, the
other may not be wired as analog.