UMI-B1 UL Series Inverter Communication protocol
128
The command sent by the master:
Parameters
address
CRC check
Inverter
address
Write
command
Forward
running
If the operation is successful, the response may be as below (the same with the
command sent by the master):
Parameters
address
CRC check
Inverter
address
Write
command
Forward
running
Set the Max. Output frequency of the inverter with the address of 03H to 100Hz.
Name
Function
code
Description
Setting
range
Default
value
Modify
Serial
No.
Max. output
frequency
P00.04–600.00 Hz (400.00 Hz)
10.00–600.00
50.00 Hz 3.
P00.03
See the figures behind the radix point, the fieldbus ratio value of the Max. output
frequency (P00.03) is 100. 100Hz timed by 100 is 10000 and the corresponding hex is
2710H.
The command sent by the master:
Parameters
address
Inverter
address
Write
command
CRC check
Forward running
If the operation is successful, the response may be as below (the same with the
command sent by the master):
Parameters
address
Inverter
address
Write
command
CRC check
Forward running
Note: the blank in the above command is for illustration. The blank cannot be added in
the actual application unless the upper monitor can remove the blank by themselves.
7.3.8.3 Example of continous writing command10H
Example 1: make the inverter whose address is 01H run forward at 10Hz. Refer to the
instruction of 2000H and 0001. Set the address of "communication setting frequency" is
2001H and 10Hz corresponds to 03E8H. See the table below.