UMI-B1 UL Series Inverter Communication protocol
129
Communication
control
command
0006H: coast to stop (emergency
stop)
The address of
communication
setting
Communication setting frequency
(0–Fmax (unit: 0.01Hz))
PID given, range (0–1000, 1000
corresponds to100.0%)
Set P00.01 to 2 and P00.06 to 8.
The command sent to the inverter:
Inverter
address
Continuous
writing
command
Parameters
address
CRC check
Byte
number
Forward
running
10Hz
Data
number
If the response message is as below:
Continuous
writing
command
Inverter
address
Parameters
address
CRC check
Data
number
Example 2: set the ACC time of 01H inverter as 10s and the DEC time as 20s
ACC time means the time needed if the
inverter speeds up from 0Hz to the Max. One
(P00.03).
DEC time means the time needed if the
inverter speeds down from the Max. Output
frequency to 0Hz (P00.03).
UMI-B1 UL series inverters define four groups
of ACC/DEC time which can be selected by
P05. The factory default ACC/DEC time of the
inverter is the first group.
Setting range of P00.11 and P00.12:
0.0–3600.0s
The corresponding address of P00.11 is 000B, the ACC time of 10s corresponds to
0064H, and the DEC time of 20s corresponds to 00C8H.
The command sent to the inverter: