UMI-B1 UL Series Inverter Function parameters
73
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
that of P08.25.
The function is illustrated as below:
RO1, RO2
S terminal
The set count
value is reached.
The specified count
value is reached.
Setting range of P08.25: P08.2665535
Setting range of P08.26: 0P08.25
P08.27
Setting
running
time
Pre-set running time of the inverter. When the
accumulative running time achieves the set
time, the multi-function digital output
terminals will output the signal of "running
time arrival".
Setting range: 065535min
0m
P08.28
Time of
fault reset
The time of the fault reset: set the fault reset
time by selecting this function. If the reset
time exceeds this set value, the inverter will
stop for the fault and wait to be repaired.
The interval time of the fault reset: The
interval between the time when the fault
occurs and the time when the reset action
occurs.
Setting range of P08.28: 010
Setting range of P08.29: 0.1100.0s
0
P08.29
Interval
time of
automatic
fault reset
1.0s
P08.30
Frequency
decreasing
ratio in
drop
control
The output frequency of the inverter changes
as the load. And it is mainly used to balance
the power when several inverters drive one
load.
Setting range: 0.0050.00Hz
0.00Hz
P08.32
FDT1
electrical
level
detection
value
When the output frequency exceeds the
corresponding frequency of FDT electrical
level, the multi-function digital output
terminals will output the signal of "frequency
level detect FDT" until the output frequency
decreases to a value lower than (FDT
electrical levelFDT retention detection
value) the corresponding frequency, the
signal is invalid. Below is the waveform
diagram:
60.00Hz
P08.33
FDT1
retention
detection
value
5.0%
P08.34
FDT2
electrical
60.00Hz