UMI-B1 UL Series Inverter Function parameters
74
Detailed instruction of parameters
Output frequency
FDT electrical level
FDT retention
Time
Time
Y, RO1, RO2
Setting range of P08.32: 0.00Hz–P00.03
(the Max. frequency)
Setting range of P08.33 and P08.35:
0.0–100.0%
Setting range of P08.34: 0.00Hz–P00.03
(the Max. frequency)
FDT2
retention
detection
value
Frequency
arrival
detection
range
When the output frequency is among the
below or above range of the set frequency,
the multi-function digital output terminal will
output the signal of "frequency arrival", see
the diagram below for detailed information:
Y
RO1, RO2
,
Output frequency
Set frequency
Detectionn range
Time
Time
The setting range: 0.00Hz–P00.03 (the Max.
frequency)
This parameter is used to control the internal
braking unit.
0: Disabled
1: Enabled
Note: Only applied to internal braking unit.
Energy
braking
threshold
voltage
After setting the original bus voltage of
energy braking, you can adjust the voltage to
implement load braking. The factory changes
with the voltage level.