UMI-B1 UL Series Inverter Function parameters
74
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
level
detection
value
Output frequency
FDT electrical level
FDT retention
Time
Time
Y, RO1, RO2
Setting range of P08.32: 0.00HzP00.03
(the Max. frequency)
Setting range of P08.33 and P08.35:
0.0100.0%
Setting range of P08.34: 0.00HzP00.03
(the Max. frequency)
P08.35
FDT2
retention
detection
value
5.0%
P08.36
Frequency
arrival
detection
range
When the output frequency is among the
below or above range of the set frequency,
the multi-function digital output terminal will
output the signal of "frequency arrival", see
the diagram below for detailed information:
Y
RO1, RO2
,
Output frequency
Set frequency
Detectionn range
Time
Time
The setting range: 0.00HzP00.03 (the Max.
frequency)
0.00Hz
P08.37
Energy
Braking
enable
This parameter is used to control the internal
braking unit.
0: Disabled
1: Enabled
Note: Only applied to internal braking unit.
0
P08.38
Energy
braking
threshold
voltage
After setting the original bus voltage of
energy braking, you can adjust the voltage to
implement load braking. The factory changes
with the voltage level.
220V
voltage:
380.0V
460V
voltage:
740.0V