UMI-B1 UL Series Inverter Function parameters
88
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
point at sudden power
loss
Note: 1. Adjust the parameter properly to
avoid the stopping caused by inverter
protection during the switching of the grid.
2. Prohibit the input phase protection to
enable this function.
P11.03
Overvoltag
e stall
protection
0: Disabled
1: Enabled
Output
current
Overvoltage
small point
Output
frequency
Time
Time
1
P11.04
Overvoltag
e stall
voltage
protection
120150% (standard bus voltage)
(460V)
120%
120150% (standard bus voltage)
(220V)
115%
P11.05
Current
limit action
The actual increasing ratio is less than the
ratio of output frequency because of the big
load during ACC running. It is necessary to
take measures to avoid overcurrent fault and
the inverter trips.
During the running of the inverter, this
function will detect the output current and
compare it with the limit level defined in
P11.06. If it exceeds the level, the inverter will
run at stable frequency in ACC running, or the
inverter will derate to run during the constant
running. If it exceeds the level continuously,
the output frequency will keep on decreasing
to the lower limit. If the output current is
detected to be lower than the limit level, the
inverter will accelerate to run.
0x01
P11.06
Automatic
current
limit level
160.0%
P11.07
The
decreasing
ratio during
current
limit
10.00
Hz/s