UMI-B1 UL Series Inverter Function parameters
89
Detailed instruction of parameters
Output frequency
Output current
Limit point
Set frequency
ACC
Time
Time
Constant
speed
Setting range of P11.05:
0: current limit invalid
1: current limit valid
2: current limit is invalid during constant
speed
Setting range of P11.05: 0x00–0x12
Setting range of P11.06: 50.0–200.0%
Setting range of P11.07: 0.00–50.00Hz/s
Overload
pre-alarm
of the
motor/
inverter
The output current of the inverter or the motor
is above P11.09 and the lasting time is
beyond P11.10, overload pre-alarm will be
output.
Output current
Overload
pre-alarm point
Time
Time
Pre-alarm
time
Pre-alarm
time
Y, RO1, RO2
Setting range of P11.08:
Enable and define the overload pre-alarm of
the inverter or the motor.
Setting range: 0x000–0x131
LED ones:
0: Overload pre-alarm of the motor, comply
with the rated current of the motor
1: Overload pre-alarm of the inverter, comply
with the rated current of the inverter
LED tens:
0: The inverter continues to work after
underload pre-alarm
Overload
pre-alarm
test level
Overload
pre-alarm
detection
time