UMI-B1 UL Series Inverter Function parameters
90
Detailed instruction of parameters
1: The inverter continues to work after
underload pre-alarm and the inverter stops to
run after overload fault
2: The inverter continues to work after
overload pre-alarm and the inverter stops to
run after underload fault
3. The inverter stops when overloading or
underloading.
LED hundreds :
0: Detection all the time
1: Detection in constant running
Setting range of P11.09: P11.11–200%
Setting range of P11.10: 0.1–3600.0s
Detection
level of the
underload
pre-alarm
If the inverter current or the output current is
lower than P11.11, and its lasting time is
beyond P11.12, the inverter will output
underload pre-alarm.
Setting range of P11.11: 0–P11.09
Setting range of P11.12: 0.1–3600.0s
Detection
time of the
underload
pre-alarm
Output
terminal
action
selection
during fault
Select the action of fault output terminals on
undervoltage and fault reset.
0x00–0x11
LED ones:
0: Action under fault undervoltage
1: No action under fault undervoltage
LED tens:
0: Action during the automatic reset
1: No action during the automatic reset
Speed
deviation
detection
0.0–50.0%
Set the speed deviation detection time.
Speed
deviation
detection
time
This parameter is used to set the speed
deviation detection time.