UMI-B1 UL Series Inverter Function parameters
94
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
responds to the reading command of the
upper monitor. The communication efficiency
can be increased in this mode.
LED tens: (reserved)
0: Communication encrypting is invalid
1: Communication encrypting is valid
P14.07
Reserved
P14.08
Reserved
P17 Group Monitoring function
P17.00
Setting
frequency
Display current set frequency of the inverter
Range: 0.00HzP00.03
P17.01
Output
frequency
Display current output frequency of the
inverter
Range: 0.00HzP00.03
P17.02
Ramp
reference
frequency
Display current ramp reference frequency of
the inverter
Range: 0.00HzP00.03
P17.03
Output
voltage
Display current output voltage of the inverter
Range: 01200V
P17.04
Output
current
Display current output current of the inverter
Range: 0.05000.0A
P17.05
Motor
speed
Display the rotation speed of the motor.
Range: 065535RPM
P17.06
Torque
current
Display current torque current of the inverter
Range: 0.05000.0A
P17.07
Magnetize
d current
Display current magnetized current of the
inverter
Range: 0.05000.0A
P17.08
Motor
power
Display current power of the motor.
Setting range: -300.0%300.0%
(the rated current of the motor)
P17.09
Output
Display the current output torque of the