UMI-B1 UL Series Inverter Function parameters
95
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
torque
inverter.
Range: -250.0250.0%
P17.10
The motor
frequency
evaluation
Evaluate the motor rotor frequency on open
loop vector
Range: 0.00 P00.03
P17.11
DC bus
voltage
Display current DC bus voltage of the inverter
Range: 0.02000.0V
P17.12
Switch
input
terminals
state
Display current Switch input terminals state of
the inverter
Range: 000000FF
P17.13
Switch
output
terminals
state
Display current Switch output terminals state
of the inverter
Range: 0000000F
P17.14
Digital
adjustment
Display the adjustment through the keypad of
the inverter.
Range: 0.00HzP00.03
P17.15
Torque
reference
Display the torque reference, the percentage
to the current rated torque of the motor.
Setting range: -300.0%300.0%
(the rated current of the motor)
P17.16
Linear
speed
Display the current linear speed of the
inverter.
Range: 065535
P17.17
Reserved
P17.18
Counting
value
Display the current counting number of the
inverter.
Range: 065535
P17.19
AI1 input
voltage
Display analog AI1 input signal
Range: 0.0010.00V