IM 50.560CA UA (B/4-03) 23
DEPOLOX
®
3 PLUS RESIDUAL ANALYZER
DEPOLOX 3 PLUS WITH BARE TWO ELECTRODE SENSOR KIT - WIRING
50.560.155.045
ISSUE 0 1-03
NOTE: FIELD WIRING (NOT BY USF/W&T) MUST CONFORM TO LOCAL ELECTRICAL CODES.
1278 349105 6 11 12
L1 L2/N PE
37 38 39 32 3031 33 25 26 2934 35 36 27 28
AB-+
CAUTION: CONSIDER
TENSION MODULE !
POWER SENSOR
FREE CHLORINE
TEMPER-
ATURE
CELL
DIGITAL
IN
mA-
OUT
CHLORINE
RS485-BUS
WH
BN
123
132
L1 L2/N PE
2 ELECTRODE
DEPOLOX 3
WETSIDE
IF SAMPLE WATER STOP
CONTACT IS OPEN
e.g. FLOW CONTROL
(OPTION)
TO LINE RECORDER, PLC
OR SCADA-SYSTEM
BN = BROWN
WH = WHITE
COLOR FROM CABLE
115V AC
230V AC
50/60 Hz
LINE VOLTAGE
POWER
-mA
+mA
3 COND.
14 AWG 32 AWG
2 COND.
2 COND./SHD
20 AWG
2 COND./SHD
20 AWG