49Installation and maintenance instructions ecoTEC 0020029172_03
10 Replacing components
The tasks listed below in this section may be carried out
only by a qualified heating engineer.
Only use genuine spare parts for repairs.
Make sure the parts are correctly fitted and that their
original position and alignment are retained.
10.1 Safety instructions
d
Danger!
Each time components are replaced, comply
with the safety instructions below for your own
safety and to avoid damage to the boiler.
Take the boiler out of operation.
e
Danger!
Risk of fatal electric shock through contact
with live connections!
Disconnect the boiler from the power mains by
de-energising the boiler using an isolating
device with a contact opening of at least 3 mm
(e.g. fuses or power switches).
Close the gas isolation valve and the service valves in
the heating flow and return.
Close the service valve in the cold water supply pipe.
Empty the boiler if you want to replace water-bearing
components of the boiler!
Make sure that water does not drip on live
components (e.g. the electronic box)!
Use only new seals and O-rings!
After completing the work, perform a tightness check
and function check (see Chapter 6.4)
10.2 Replacing the burner
d
Danger!
Before replacing the component, observe the
safety information in Chapter 10.1.
Dismount the compact thermal module as described in
Chapter 8.3.1.
1
Fig. 10.1 Replacing the burner
Release the four screws (1) on the burner, and remove
the burner.
Mount the new burner with a new seal. Make sure the
seal notch for the inspection glass fits into the notch
of the burner flange.
Re-install the compact thermal module as described in
Chapter 8.3.4.
After completing the work, perform a gas-tightness
check and function check (see Chapter 8.10).
10.3 Replacing the fan or the gas valve
d
Danger!
Before replacing the component, observe the
safety information in Chapter 10.1.
Disconnect the boiler from the power mains as
described in Chapter 10.1, and close the gas isolation
valve.
Remove the air intake pipe (1, Fig. 8.2).
Disconnect the gas supply pipe at the gas valve
(6, Fig. 10.3).
Replacing components 10