EasyManuals Logo

Vaillant VWZ AI User Manual

Vaillant VWZ AI
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #33 background imageLoading...
Page #33 background image
Appendix
0020291573_00 Heat pump control interface module Installation instructions 31
Code Meaning Cause
Remedy
F.729 Compressor outlet temperature
too low
The compressor outlet temperature
is lower than 0 °C for more than 10
minutes or the compressor outlet
temperature is lower than -10 °C
even though the heat pump is in the
operating characteristics.
Checking the high-pressure sensor
Checking that the EEV is working
correctly
Checking for condensate leaking
from the temperature sensor (under-
cooling)
Check whether the 4-port diverter
valve is in the intermediate position
Checking the refrigerant volume for
overfilling
F.731 High-pressure switch open Refrigerant pressure too high. The
integrated high-pressure switch
in the outdoor unit has tripped at
41.5 bar (g) or 42.5 bar (abs)
Insufficient energy output via the
condenser
Purging the building circuit
Too low a volume flow as a result
of closing single room controls in an
underfloor heating system
Check that the dirt filter that is in
place is permeable
Refrigerant flow rate too low (e.g.
electronic expansion valve defective,
4-port diverter valve is mechanically
blocked, filter is blocked). Inform
customer service.
Cooling mode: Check the fan unit for
dirt
Check the high-pressure switch and
high-pressure sensor
Reset the high-pressure switch and
carry out a manual reset on the
product.
F.732 Compressor outlet temperature
too high
The compressor outlet temperature is
above 110 °C:
Application limits exceeded
EEV does not work or does not open
correctly
Refrigerant volume too low (frequent
defrosting due to extremely low
evaporation temperatures)
Check the compressor inlet sensor
and outlet sensor
Check the compressor outlet temper-
ature sensor (TT135)
Check the EEV (does the EEV
move to the limit stop? Use the
sensor/actuator test)
Check the refrigerant volume (see
Technical data)
Carry out a leak-tightness test
Check whether the service valves on
the outdoor unit are open.
F.733 Evaporation temperature too low Insufficient air volume flow through
the outdoor unit's heat exchanger
(heating mode) leads to an insuffi-
cient energy input in the environment
circuit (heating mode) or building cir-
cuit (cooling mode)
Refrigerant volume too low
If the building circuit contains ther-
mostatic valves, check that they are
suitable for cooling mode (check
volume flow in cooling mode)
Check the fan unit for dirt
Check the EEV (does the EEV
move to the limit stop? Use the
sensor/actuator test)
Check the compressor inlet sensor
Check the refrigerant volume
F.734 Condensation temperature too low The temperature in the heating
circuit is too low, outside of the
operating characteristics
Refrigerant volume too low
Check the EEV (does the EEV
move to the limit stop? Use the
sensor/actuator test)
Check the compressor inlet sensor
Check the refrigerant filling volume
(see technical data)
Check whether the 4-port diverter
valve is in an intermediate position
and is not correctly switched
Checking the high-pressure sensor
Check the pressure sensor in the
heating circuit

Table of Contents

Other manuals for Vaillant VWZ AI

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vaillant VWZ AI and is the answer not in the manual?

Vaillant VWZ AI Specifications

General IconGeneral
BrandVaillant
ModelVWZ AI
CategoryControl Unit
LanguageEnglish

Related product manuals