EasyManuals Logo

Vaillant VWZ AI User Manual

Vaillant VWZ AI
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #34 background imageLoading...
Page #34 background image
Appendix
32 Installation instructions Heat pump control interface module 0020291573_00
Code Meaning Cause
Remedy
F.735 Evaporation temperature too high Temperature in the environment
circuit (heating mode) or building
circuit (cooling mode) too high for
compressor operation
Feed-in of external heat into the
environment circuit due to increased
fan speed
Check the system temperatures
Check the refrigerant filling volume
for overfilling
Check the EEV (does the EEV
move to the limit stop? Use
sensor/actuator test)
Check the sensor for the evaporation
temperature (depending on the
position of the 4-port diverter valve)
Check the volume flow in cooling
mode
Check the air volume flow in heating
mode
F.737 Condensation temperature too
high
Temperature in the environment
circuit (cooling mode) or building
circuit (heating mode) too high for
compressor operation
Feed-in of external heat into the
building circuit
Refrigerant circuit overfilled
Insufficient flow rate in the building
circuit
Reduce or stop the external heat
that is entering
Check the back-up heater (heats
up even though it is off in the
sensor/actuator test?)
Check the EEV (does the EEV
move to the limit stop? Use the
sensor/actuator test)
Check the compressor outlet sensor,
compressor outlet temperature
sensor (TT135) and high-pressure
sensor
Check the refrigerant filling volume
for overfilling
Check whether the service valves on
the outdoor unit are open.
Check the air volume flow in cooling
mode for sufficient flow rate
Checking the heating pump
Check the building circuit flow rate
F.741 Building circuit: Return temp. too
low
During the de-icing, the return tem-
perature falls below 13 °C
Ensure the minimum installation
volume is maintained; if required,
install a series return cylinder
The fault message is displayed until
the return temperature increases to
above 20 °C.
Activate the electric back-up heater
in the product's control panel and
in the system control in order to
increase the return temperature. The
compressor is blocked while the fault
message is present.
F.752 Fault: Frequency converter Internal electronics fault on the in-
verter PCB
Mains voltage outside of 70 V282 V
Check the integrity of the power sup-
ply cables and compressor connec-
tion cables
The plugs must audibly click into
place.
Check the cable
Check the mains voltage
The mains voltage must be between
195 V and 253 V.
Check the phases
Replace the frequency converter, if
required
F.753 Connection fault: Freq. conv.
n.recogn.
Missing communication between the
frequency converter and the outdoor
unit's control PCB
Check the integrity of the cable
harness and plug connection and,
if required, replace them
Check the frequency converter by
actuating the compressor safety
relay
Read the assigned parameters for
the frequency converter and check
whether values are displayed

Table of Contents

Other manuals for Vaillant VWZ AI

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vaillant VWZ AI and is the answer not in the manual?

Vaillant VWZ AI Specifications

General IconGeneral
BrandVaillant
ModelVWZ AI
CategoryControl Unit
LanguageEnglish

Related product manuals