EasyManua.ls Logo

Val Controls I 24-AF Series - Digital Input - DI1, DI2, DI3, DI4

Val Controls I 24-AF Series
20 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DHW-UM-004
Val Controls A/S Sallingsundvej 5 DK-6715 Esbjerg N Tel. +45 7547 0600
vc@valcontrols.com www.valcontrols.com
Revision: 4
11/20
3.6 Digital input DI1, DI2, DI3, DI4
Use digital inputs to connect dry signals.
DI
+
-
Switch
+
-
DI
+
-
NAMUR
+
-
3.6.1 Terminals
DI1
39 (+)
40 (-)
DI2
41 (+)
42 (-)
DI3
43 (+)
44 (-)
DI4
45 (+)
46 (-)
3.6.2 Electrical specifications
DI Switch
Type
Switch
Cable length
20 meters
Maximum cable resistance
100 Ohm
DI NAMUR
Type
NAMUR
Sensor supply voltage
8 V
Cable length
1000 meters
Max load
600 Ohm
Rin
1040 Ohm