5 Expansion
The expansion terminals have different function depending on which expansion module is installed.
5.1 Active analogue output AO1, AO2 and Digital inputs DI5, DI6
Use the two analogue outputs to connect 4-20mA loop inputs e.g. proportional valves.
Passive 4-20mA input
-
Active AO
+
A
+
-
DI
+
-
Switch
+
-
DI
+
-
NAMUR
+
-
5.1.1 Terminals
AO1
21 (+)
22 (-)
AO2
23 (+)
24 (-)
DI5
51 (+)
52 (-)
DI6
25 (-)
26 (+)
5.1.2 Electrical specifications
AO1 AO2 Active analogue output
Max load
550 Ohm at 20mA and 20.4VDC PS2 supply
Linearity
< 0.1%
Temperature coefficient
0.015% / 1°C (Warm-up: 10 min)
DI Switch
Type
Switch
Cable length
20 meters
Maximum cable resistance
100 Ohm
DI NAMUR
Type
NAMUR
Sensor supply voltage
8 V
Cable length
1000 meters
Max load
600 Ohm
Rin
1040 Ohm