53/74
No. 466
FST error: Total timeout, position
Description
The valve did not reach the operational position within the FST total timeout
Trouble shooting
This error can be caused by:
• No supply pressure
• The valve is stuck
• The valve is moving slow
• The solenoid valve cannot be activated
It can be solved by:
• Resolve the mechanical problem
• Increase FST total timeout