EasyManua.ls Logo

Val Controls IDC24-A - Page 53

Default Icon
74 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DID-UM-002
Val Controls A/S Limfjordsvej 3 DK-6715 Esbjerg N Tel. +45 7547 0600
vc@valcontrols.com www.valcontrols.com
Revision: 10
53/74
No. 466
FST error: Total timeout, position
Description
The valve did not reach the operational position within the FST total timeout
Trouble shooting
This error can be caused by:
No supply pressure
The valve is stuck
The valve is moving slow
The solenoid valve cannot be activated
It can be solved by:
Resolve the mechanical problem
Increase FST total timeout

Related product manuals