EasyManua.ls Logo

Val Controls IHP24-A - Page 19

Val Controls IHP24-A
58 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DHP-UM-013
Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600 • Fax +45 7547 0611
vc@valcontrols.com • www.valcontrols.com
Revision: 4
19/58
resource
DEV_TYPE
[Diagnostic]
11
Value: “0x1001” – NCS_MODBUS_FF
Length: 2 bytes
Read Only
Description:
Manufacturer’s model number associated with the
resource – used by the interface defines to locate
DD file for the resource
DEV_REV
[Diagnostic]
12
Value: “0x02”
Length: 1 bytes
Read Only
Description:
Manufacturer’s revision number associated with
the resource – used by the interface defines to
locate DD file for the resource
DD_REV
[Diagnostic]
13
Value: “0x01”
Length: 1 bytes
Read Only
Description:
Revision of the DD associated with the resource –
used by an interface device to locate the DD file
for the resource.
GRANT_DENY
[Options]
14
1: Length: 1 bytes
Read Write
2: Length 1 bytes
Read Write
Description: Option for controlling access of host
computers and local control panels to operating
tuning and alarm parameters of the block.
HARD_TYPES
[Process]
15
Length: 2 bytes
Read Write
Description: The types of hardware available as
channel numbers
RESTART
[Options]
16
Length: 1 bytes
Read Write
Allows a manual restart to be initiated. Several
degrees of restart are
possible, they are:
1: Run – Normal state when running
2: Restart Resource
3: Restart with Default – Set the parameters to