Value Status: Good, Bad ..
Description: Analog Input from sensor
SCALE_LOC_IN7
[Others]
SCALE_LOC_IN_7
Value FROM_EU100 = 10000
Value FROM_EU0 = 0
Value TO_EU100 = 100
Value TO_EU0 = 0
Value Data Type = Unsigned16_10
Value Function Code = FC03 Read Holding
Register
Value REGISTER_ADDR_OF_VALUE = 7006
Value REGISTER_ADDR_OF_STATUS = 7106
Description: Internal communication settings
between valcontrols product and fieldbus interface.
If input is not used set
REGISTER_ADDR_OF_STATUS = 0, Status sub
status then changes to “Out of Service”
MOD_IN8
[Others]
MOD_IN
Length: 4 bytes, Float
Value: 0.00 100.00
Value Status: Good, Bad ..
Description: Analog Input from sensor
SCALE_LOC_IN8
[Others]
SCALE_LOC_IN_8
Value FROM_EU100 = 10000
Value FROM_EU0 = 0
Value TO_EU100 = 100
Value TO_EU0 = 0
Value Data Type = Unsigned16_10
Value Function Code = FC03 Read Holding
Register
Value REGISTER_ADDR_OF_VALUE = 7007
Value REGISTER_ADDR_OF_STATUS = 7107
Description: Internal communication settings
between valcontrols product and fieldbus interface.
If input is not used set
REGISTER_ADDR_OF_STATUS = 0, Status sub
status then changes to “Out of Service”
MOD_OUT1
[Others]
MOD_OUT
Value: 0.00 100.00
Value Status: Good, Bad ..
Value is received from AO via channel 1
Description: Analog control value such as SP that
need to be send to the Val Controls Device
SCALE_LOC_OUT1
[Others]
SCALE_LOC_OUT1
Value FROM_EU100 = 100
Value FROM_EU0 = 0