Valent VX Series Controller48
VARIABLE DESCRIPTION
ACTIVE
TEXT
INACTIVE
TEXT
BACNET MODBUS
OBJECT
INSTANCE
OBJECT
TYPE
ACCESS HYST INDEX
REGISTER
TYPE
SIZE
Binary Inputs - Read Only
Exhaust_Fan_1_
Status_Digital_Input
Exhaust Fan 1 Status Active Inactive 23 BI
ReadCOV_
NoWrite
0 24 Discrete
Occupancy_Digital_
Input
Occupancy Digital Input
Status
Active Inactive 53 BI
ReadCOV_
NoWrite
0 54 Discrete
Outside_Filter_Alarm_
Digital_Input
Outside Filter Alarm Digital
Input Status
Active Inactive 54 BI
ReadCOV_
NoWrite
0 55 Discrete
Shutdown_Alarm_
Digital_Input
Shutdown Alarm Digital
Input Status
Active Inactive 75 BI
ReadCOV_
NoWrite
0 76 Discrete
Supply_Fan_1_Status_
Digital_Input
Supply Fan 1 Status Active Inactive 78 BI
ReadCOV_
NoWrite
0 79 Discrete
Unit_Enable_Digital_
Input
Remote Unit Enable Digital
Input Status
Active Inactive 82 BI
ReadCOV_
NoWrite
0 83 Discrete
Wheel_Status_Digital_
Input
Heat Wheel Status Active Inactive 83 BI
ReadCOV_
NoWrite
0 84 Discrete
Binary Values - Read/Write - Commandable
BMS_Watchdog
BMS Watchdog command.
Used to determine comm
status. Must heartbeat
within the watchdog
timeout delay to detect
comm status.
Active Inactive 1 BV
Read_
Commandable
0 2 Coil
System_Enable
Master system enable/
disable point.
Enable Disable 2 BV
Read_
Commandable
0 3 Coil
BMS_Occupancy_
Command
Occupancy Command. True
= Unoccupied. False =
Occupied.
Unoccupy Occupy 3 BV
Read_
Commandable
0 4 Coil
Reset_All_Alarms Alarm Reset Command. Reset Normal 4 BV
Read_
Commandable
0 5 Coil
Outside_RH_Source_
BMS
Outside RH Source
Selection. True = BMS.
False = Local.
BMS Local 5 BV
Read_
Commandable
0 6 Coil
Outside_Temp_
Source_BMS
Outside Temp Source
Selection. True = BMS.
False = Local.
BMS Local 6 BV
Read_
Commandable
0 7 Coil
Return_RH_Source_
BMS
Return RH Source BMS Local 7 BV
Read_
Commandable
8 Coil
Return_Temp_Source_
BMS
Return Temp Source BMS Local 8 BV
Read_
Commandable
9 Coil
Space_1_CO2_
Source_BMS
Space 1 CO2 Source
Selection. True = BMS.
False = Local.
BMS Local 9 BV
Read_
Commandable
0 10 Coil
Space_RH_Source_
BMS
Space RH Source Selection.
True = BMS. False = Local.
BMS Local 12 BV
Read_
Commandable
0 13 Coil
Space_Static_Source_
BMS
Space Static Source
Selection. True = BMS.
False = Local.
BMS Local 13 BV
Read_
Commandable
0 14 Coil
Space_Temp_Source_
BMS
Space Temp Source
Selection. True = BMS.
False = Local.
BMS Local 14 BV
Read_
Commandable
0 15 Coil
SF_Control_Source_
BMS
Allows the BMS to control
supply fan speed. True =
BMS. False = Local.
BMS Local 56 BV
Read_
Commandable
0 19 Coil
EF_Control_Source_
BMS
Allows the BMS to control
exhaust fan speed. True =
BMS. False = Local.
BMS Local 57 BV
Read_
Commandable
0 20 Coil
OAD_Control_Source_
BMS
Allows the BMS to control
OAD position. True = BMS.
False = Local.
BMS Local 59 BV
Read_
Commandable
0 22 Coil
Appendix E: Points List