Valent VX Series Controller50
VARIABLE DESCRIPTION
ACTIVE
TEXT
INACTIVE
TEXT
BACNET MODBUS
OBJECT
INSTANCE
OBJECT
TYPE
ACCESS HYST INDEX
REGISTER
TYPE
SIZE
Compressor_4_
Enable_Digital_Output
Compressor 4 Enable
Digital Output
Active Inactive 114 BV
ReadCOV_
NoWrite
0 10167 Discrete
Condenser_Fan_1_
Digital_Output
Condenser Fan 1 Digital
Output
Active Inactive 119 BV
ReadCOV_
NoWrite
0 10172 Discrete
Condenser_Fan_2_
Digital_Output
Condenser Fan 2 Digital
Output
Active Inactive 120 BV
ReadCOV_
NoWrite
0 10173 Discrete
Condenser_Fan_3_
Digital_Output
Condenser Fan 3 Digital
Output
Active Inactive 121 BV
ReadCOV_
NoWrite
0 10174 Discrete
Exhaust_Fan_1_Start_
Stop_Digital_Output
Exhaust Fan 1 Start Stop
Digital Output
Active Inactive 127 BV
ReadCOV_
NoWrite
0 10180 Discrete
Furnace_1_Stage_1_
Digital_Output
Furnace 1 Stage 1 Digital
Output
Active Inactive 131 BV
ReadCOV_
NoWrite
0 10184 Discrete
Furnace_2_Stage_1_
Digital_Output
Furnace 2 Stage 1 Digital
Output
Active Inactive 133 BV
ReadCOV_
NoWrite
0 10186 Discrete
Heat_Wheel_Enable_
Digital_Output
Heat Wheel Enable Digital
Output
Active Inactive 163 BV
ReadCOV_
NoWrite
0 10208 Discrete
PreHeat_Enable_
Digital_Output
PreHeat Enable Digital
Output
Active Inactive 166 BV
ReadCOV_
NoWrite
0 10211 Discrete
Supply_Fan_1_Start_
Stop_Digital_Output
Supply Fan 1 Start Stop
Digital Output
Active Inactive 186 BV
ReadCOV_
NoWrite
0 10231 Discrete
BMS_Offline_Alarm.
Active
BMS Offline Alarm
(0=Normal 1=Alarm)
Alarm Normal 313 BV
ReadCOV_
NoWrite
0 10264 Discrete
Circuit_A_Discharge_
Pressure_Analog_
Input_Alarm.Active
Circuit A Discharge
Pressure Analog Input
Alarm
Alarm Normal 315 BV
ReadCOV_
NoWrite
10266 Discrete
Circuit_A_Discharge_
Temp_Analog_Input_
Alarm.Active
Circuit A Discharge Temp
Analog Input Alarm
Alarm Normal 316 BV
ReadCOV_
NoWrite
10267 Discrete
Circuit_A_Suction_
Pressure_Analog_
Input_Alarm.Active
Circuit A Suction Pressure
Analog Input Alarm
Alarm Normal 319 BV
ReadCOV_
NoWrite
10270 Discrete
Circuit_A_Suction_
Temp_Analog_Input_
Alarm.Active
Circuit A Suction Temp
Analog Input Alarm
Alarm Normal 320 BV
ReadCOV_
NoWrite
10271 Discrete
Circuit_B_Discharge_
Pressure_Analog_
Input_Alarm.Active
Circuit B Discharge
Pressure Analog Input
Alarm
Alarm Normal 324 BV
ReadCOV_
NoWrite
10275 Discrete
Cold_Coil_1_
Temperature_Sensor_
Alarm.Active
Cold Coil 1 Temperature
Sensor Alarm (0=Normal
1=Alarm)
Alarm Normal 387 BV
ReadCOV_
NoWrite
0 10338 Discrete
Comp_Maintenance_
Alarm.Active
Comp Maintenance Alarm
(0=Normal 1=Alarm)
Alarm Normal 411 BV
ReadCOV_
NoWrite
0 10362 Discrete
Exhaust_Fan_1_Alarm.
Active
Exhaust Fan 1 Alarm
(0=Normal 1=Alarm)
Alarm Normal 423 BV
ReadCOV_
NoWrite
0 10373 Discrete
Expansion_Board_1_
Alarm.Active
Expansion Board 1 Alarm
(0=Normal 1=Alarm)
Alarm Normal 434 BV
ReadCOV_
NoWrite
0 10384 Discrete
Expansion_Board_2_
Alarm.Active
Expansion Board 2 Alarm
(0=Normal 1=Alarm)
Alarm Normal 435 BV
ReadCOV_
NoWrite
0 10385 Discrete
Expansion_Board_3_
Alarm.Active
Expansion Board 3 Alarm
(0=Normal 1=Alarm)
Alarm Normal 436 BV
ReadCOV_
NoWrite
0 10386 Discrete
Internal_Board_Temp_
Alarm.Active
Internal Board Temp Alarm
(0=Normal 1=Alarm)
Alarm Normal 498 BV
ReadCOV_
NoWrite
0 10448 Discrete
Multi_Channel_Conf_
Alarm.Active
Multi Channel Conf Alarm
(0=Normal 1=Alarm)
Alarm Normal 503 BV
ReadCOV_
NoWrite
0 10453 Discrete
Outside_Air_
Temperature_Sensor_
Alarm.Active
Outside Air Temperature
Sensor Alarm (0=Normal
1=Alarm)
Alarm Normal 507 BV
ReadCOV_
NoWrite
0 10457 Discrete
Outside_Filter_Alarm.
Active
Outside Filter Alarm
(0=Normal 1=Alarm)
Alarm Normal 508 BV
ReadCOV_
NoWrite
0 10458 Discrete
Outside_RH_Sensor_
Alarm.Active
Outside RH Sensor Alarm
(0=Normal 1=Alarm)
Alarm Normal 509 BV
ReadCOV_
NoWrite
0 10459 Discrete
Space_CO2_1_
Analog_Input_Alarm.
Active
Space CO2 1 Analog Input
Alarm (0=Normal 1=Alarm)
Alarm Normal 535 BV
ReadCOV_
NoWrite
0 10485 Discrete
Space_High_Static_
Alarm.Active
Space High Static Alarm
(0=Normal 1=Alarm)
Alarm Normal 537 BV
ReadCOV_
NoWrite
0 10487 Discrete
Appendix E: Points List

Other manuals for valent VX Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the valent VX Series and is the answer not in the manual?

valent VX Series Specifications

General IconGeneral
Brandvalent
ModelVX Series
CategoryAir Handlers
LanguageEnglish

Related product manuals