Valent VX Series Controller52
VARIABLE DESCRIPTION
ACTIVE
TEXT
INACTIVE
TEXT
BACNET MODBUS
OBJECT
INSTANCE
OBJECT
TYPE
ACCESS HYST INDEX
REGISTER
TYPE
SIZE
Al_LOP_A_EVD_1.
Active
EVD Low Operating
Pressure Alarm - Valve 1
(0=Normal 1=Alarm)
Alarm Normal 604 BV
ReadCOV_
NoWrite
0 10554 Discrete
Al_Low_SH_A_EVD_1.
Active
EVD Low SuperHeat
Alarm - Valve 1 (0=Normal
1=Alarm)
Alarm Normal 606 BV
ReadCOV_
NoWrite
0 10556 Discrete
Al_LowDeltaP_
COMP_1.Active
Compressor Envelope -
Low Pressure DeltaAlarm
(0=Normal 1=Alarm)
Alarm Normal 608 BV
ReadCOV_
NoWrite
0 10558 Discrete
Al_LowRatioP_
COMP_1.Active
Compressor Envelope -
Low Pressure Ratio Alarm
(0=Normal 1=Alarm)
Alarm Normal 609 BV
ReadCOV_
NoWrite
0 10559 Discrete
Al_LowSuct_A_EVD_1.
Active
Low Suction Refrigerant
Temperature - Valve 1
(0=Normal 1=Alarm)
Alarm Normal 610 BV
ReadCOV_
NoWrite
0 10560 Discrete
Al_MOP_A_EVD_1.
Active
EVD Max Operating
Pressure Alarm - Valve 1
(0=Normal 1=Alarm)
Alarm Normal 612 BV
ReadCOV_
NoWrite
0 10562 Discrete
Al_S1_EVD_1.Active
EVD-S1 Suction Pressure
Sensor Alarm (0=Normal
1=Alarm)
Alarm Normal 614 BV
ReadCOV_
NoWrite
0 10564 Discrete
Al_S2_EVD_1.Active
EVD-S2 Suction
Temperature Sensor Alarm
(0=Normal 1=Alarm)
Alarm Normal 615 BV
ReadCOV_
NoWrite
0 10565 Discrete
Al_S4_EVD_1.Active
EVD-S4 Discharge
Temperature Sensor Alarm
(0=Normal 1=Alarm)
Alarm Normal 617 BV
ReadCOV_
NoWrite
0 10567 Discrete
Al_SuctHiP_COMP_1.
Active
Compressor Envelope -
SuctHiP_COMP (0=Normal
1=Alarm)
Alarm Normal 618 BV
ReadCOV_
NoWrite
0 10568 Discrete
Al_SuctLowP_
COMP_1.Active
Compressor Envelope
- SuctLowP_COMP
(0=Normal 1=Alarm)
Alarm Normal 619 BV
ReadCOV_
NoWrite
0 10569 Discrete
HP_Defrost_Active.
Active
Heat Pump Defrost Alarm Alarm Normal 631 BV
ReadCOV_
NoWrite
10579 Discrete
Comp_Staging_Order_
Skipped.Active
Compressor Staging
Order is Skipped Warning
(0=Normal 1=Alarm)
Alarm Normal 632 BV
ReadCOV_
NoWrite
0 10580 Discrete
Heat_Pump_Heating_
Lock_Out_Alarm.
Active
Heat Pump Heating Locked
Out Alarm
Alarm Normal 633 BV
ReadCOV_
NoWrite
10581 Discrete
EVD_PrePosition_
Alarm_1.Active
Unexpected EEV Position
(0=Normal 1=Alarm)
Alarm Normal 634 BV
ReadCOV_
NoWrite
0 10582 Discrete
ER_Wheel_High_
DP.Active
Energy Recovery Wheel
high differential pressure
(0=Normal 1=Alarm)
Alarm Normal 731 BV
ReadCOV_
NoWrite
0 10679 Discrete
OAD_Feedback_Error_
Not_Economizing.
Active
Feedback indicates OAD
is not opening during
economizer
Alarm Normal 741 BV
ReadCOV_
NoWrite
10690 Discrete
OAD_Feedback_Error_
Economizing.Active
Feedback indicates OAD
is open
Alarm Normal 742 BV
ReadCOV_
NoWrite
10692 Discrete
OAD_Feedback_Error_
OAD_Not_Modulating.
Active
Feedback indicates the OAD
is not modulating
Alarm Normal 743 BV
ReadCOV_
NoWrite
10694 Discrete
OAD_Feedback_Error_
Excess_OA.Active
Feedback indicates the OAD
is not closing
Alarm Normal 744 BV
ReadCOV_
NoWrite
10696 Discrete
Appendix E: Points List

Other manuals for valent VX Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the valent VX Series and is the answer not in the manual?

valent VX Series Specifications

General IconGeneral
Brandvalent
ModelVX Series
CategoryAir Handlers
LanguageEnglish

Related product manuals