Valent VX Series Controller 53
VARIABLE DESCRIPTION
ACTIVE
TEXT
INACTIVE
TEXT
BACNET MODBUS
OBJECT
INSTANCE
OBJECT
TYPE
ACCESS HYST INDEX
REGISTER
TYPE
SIZE
Binary Values - Commandable
Aux_BMS_Digital_
Output_1
BMS Commanded auxilary
digital output
Active Inactive 207 BV
ReadCOV_
Commandable
0 24 Coil
Aux_BMS_Digital_
Output_2
BMS Commanded auxilary
digital output
Active Inactive 208 BV
ReadCOV_
Commandable
0 25 Coil
Aux_BMS_Digital_
Output_3
BMS Commanded auxilary
digital output
Active Inactive 209 BV
ReadCOV_
Commandable
0 26 Coil
Aux_BMS_Digital_
Output_4
BMS Commanded auxilary
digital output
Active Inactive 210 BV
ReadCOV_
Commandable
0 27 Coil
Aux_BMS_Digital_
Output_5
BMS Commanded auxilary
digital output
Active Inactive 211 BV
ReadCOV_
Commandable
0 28 Coil
Aux_BMS_Digital_
Output_6
BMS Commanded auxilary
digital output
Active Inactive 212 BV
ReadCOV_
Commandable
0 29 Coil
Integer Values - Read Only
Allow_Fan_Delay_
Remaining
Startup Sequence Fan
Damper Delay. Time before
enabling Fan startup
sequence.
1 IV
ReadCOV_
NoWrite
1 30182 Input 1
Supply_Fan_Delay_
Remaining
Supply Fan startup
sequence. Time before
starting supply fan.
2 IV
ReadCOV_
NoWrite
1 30184 Input 1
Exhaust_Fan_Delay_
Remaining
Exhaust Fan startup
sequence. Time before
starting exhaust fan.
3 IV
ReadCOV_
NoWrite
1 30186 Input 1
LatestAlm
Most recent alarm. See
alarm table.
7 IV
ReadCOV_
NoWrite
1 30195 Input 2
Large Board Points
Binary Values - Read Only
High_Low_Press_
Circ_A_Alarm.Active
High Low Pressure Switch
Alarm Circuit A
Alarm Normal 733 BV
ReadCOV_
NoWrite
0 10682 Discrete
High_Low_Press_
Circ_B_Alarm.Active
High Low Pressure Switch
Alarm Circuit B
Alarm Normal 734 BV
ReadCOV_
NoWrite
0 10683 Discrete
High_Low_Press_
Circ_C_Alarm.Active
High Low Pressure Switch
Alarm Circuit A
Alarm Normal 735 BV
ReadCOV_
NoWrite
0 10684 Discrete
High_Low_Press_
Circ_D_Alarm.Active
High Low Pressure Switch
Alarm Circuit B
Alarm Normal 736 BV
ReadCOV_
NoWrite
0 10685 Discrete
High_Low_Press_
Circ_C_Alarm.Active
High Low Pressure Switch
Alarm Circuit C
Alarm Normal 735 BV
ReadCOV_
NoWrite
0 10684 Discrete
High_Low_Press_
Circ_D_Alarm.Active
High Low Pressure Switch
Alarm Circuit D
Alarm Normal 736 BV
ReadCOV_
NoWrite
0 10685 Discrete
Greentrol_1_Alarm.
Active
Greentrol Device Alarm Alarm Normal 737 BV
ReadCOV_
NoWrite
0 10686 Discrete
Greentrol_2_Alarm.
Active
Greentrol Device Alarm Alarm Normal 738 BV
ReadCOV_
NoWrite
0 10687 Discrete
Greentrol_3_Alarm.
Active
Greentrol Device Alarm Alarm Normal 739 BV
ReadCOV_
NoWrite
0 10688 Discrete
Medium Board Points
Analog Inputs - Read Only
Mixed_Temp_Analog_
Input
Mixed Temperature 35 AI
ReadCOV_
NoWrite
0.1 30263 Input 2
Exhaust_Fan_Speed_
Analog_Input
Exhaust Fan Speed Remote
Command Analog Input
value
143 AI
ReadCOV_
NoWrite
1 30455 Input 2
Supply_Fan_Speed_
Analog_Input
Supply Fan Speed Remote
Command Analog Input
value
155 AI
ReadCOV_
NoWrite
1 30461 Input 2
Appendix E: Points List