Valent VX Series Controller54
Appendix E: Points List
VARIABLE DESCRIPTION
ACTIVE
TEXT
INACTIVE
TEXT
BACNET MODBUS
OBJECT
INSTANCE
OBJECT
TYPE
ACCESS HYST INDEX
REGISTER
TYPE
SIZE
Binary Inputs - Read Only
Comp_Circ_A_High_
Pressure_Digital_Input
Circuit A High Pressure
Switch
Active Inactive 3 BI
ReadCOV_
NoWrite
0 10052 Discrete
Comp_Circ_A_Low_
Pressure_Digital_Input
Circuit A Low Pressure
Switch
Active Inactive 4 BI
ReadCOV_
NoWrite
0 10053 Discrete
Comp_Circ_B_High_
Pressure_Digital_Input
Circuit B High Pressure
Switch
Active Inactive 5 BI
ReadCOV_
NoWrite
0 10054 Discrete
Comp_Circ_B_Low_
Pressure_Digital_Input
Circuit B Low Pressure
Switch
Active Inactive 6 BI
ReadCOV_
NoWrite
0 10055 Discrete
Drain_Pan_Alarm_
Digital_Input
Drain Pan Alarm Digital
Input Status
Active Inactive 21 BI
ReadCOV_
NoWrite
0 10070 Discrete
EAD_End_Switch_
Digital_Input
Exhaust Air Damper End
Switch Digital Input Status
Active Inactive 22 BI
ReadCOV_
NoWrite
0 10071 Discrete
OAD_End_Switch_
Digital_Input
OAD End Switch Digital
Input Status
Active Inactive 52 BI
ReadCOV_
NoWrite
0 10101 Discrete
Binary Values - Read Only
Condenser_Fan_5_
Digital_Output
Condenser Fan 5 Digital
Output
Active Inactive 123 BV
ReadCOV_
NoWrite
0 10176 Discrete
Condenser_Fan_6_
Digital_Output
Condenser Fan 6 Digital
Output
Active Inactive 124 BV
ReadCOV_
NoWrite
0 10177 Discrete
Condenser_Fan_7_
Digital_Output
Condenser Fan 7 Digital
Output
Active Inactive 125 BV
ReadCOV_
NoWrite
0 10178 Discrete
Comp_Circ_A_High_
Pressure_Alarm.Active
Comp Circ A High Pressure
Alarm (0=Normal 1=Alarm)
Alarm Normal 395 BV
ReadCOV_
NoWrite
0 10346 Discrete
Comp_Circ_A_Low_
Pressure_Alarm.Active
Comp Circ A Low Pressure
Alarm (0=Normal 1=Alarm)
Alarm Normal 396 BV
ReadCOV_
NoWrite
0 10347 Discrete
Comp_Circ_B_High_
Pressure_Alarm.Active
Comp Circ B High Pressure
Alarm (0=Normal 1=Alarm)
Alarm Normal 397 BV
ReadCOV_
NoWrite
0 10348 Discrete
Comp_Circ_B_Low_
Pressure_Alarm.Active
Comp Circ B Low Pressure
Alarm (0=Normal 1=Alarm)
Alarm Normal 398 BV
ReadCOV_
NoWrite
0 10349 Discrete
Damper_End_Switch_
Alarm.Active
Damper End Switch Alarm
(0=Normal 1=Alarm)
Alarm Normal 420 BV
ReadCOV_
NoWrite
0 10371 Discrete
Drain_Pan_Alarm.
Active
Drain Pan Alarm (0=Normal
1=Alarm)
Alarm Normal 422 BV
ReadCOV_
NoWrite
0 10372 Discrete
Exhaust_Fan_1_AMD_
analog_input_Alarm.
Active
Exhaust Fan 1 CFM Analog
Input Alarm (0=Normal
1=Alarm)
Alarm Normal 424 BV
ReadCOV_
NoWrite
0 10374 Discrete
Freeze_Stat_Alarm.
Active
Freeze Stat Alarm
(0=Normal 1=Alarm)
Alarm Normal 441 BV
ReadCOV_
NoWrite
0 10391 Discrete
Mixed_Temperature_
Sensor_Alarm.Active
Mixed Temperature Sensor
Alarm (0=Normal 1=Alarm)
Alarm Normal 502 BV
ReadCOV_
NoWrite
0 10452 Discrete
OAD_AMD_analog_
input_Alarm.Active
OAD CFM Analog Input
Alarm (0=Normal 1=Alarm)
Alarm Normal 506 BV
ReadCOV_
NoWrite
0 10456 Discrete