EasyManua.ls Logo

Valeo Thermo E+ 120 - Fault Lock-Out

Valeo Thermo E+ 120
65 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
404
Thermo E+ 120/200/320 4 Heater functions
4.4 Fault lock-out and heater lock-out
A distinction is made between fault lock-out and heater
lock-out.
The lock-outs protect the heater and the surrounding
vehicle assemblies against sequence errors after a failure
or a malfunction of individual heater components.
In a heater lock-out safety-related components are
affected by the failure or malfunction. It may only be
released by Valeo trained personnel after eliminating the
cause.
Each fault lock-out and heater lock-out is stored in the
control device.
4.4.1 Fault lock-out
If one of the malfunctions listed below occurs, the heater
will initiate a fault shut-down, followed by a fault lock-out.
Depending on the error timing, no purge cycle or a 120
seconds purge cycle will be executed.
Flash impulses are outputted via the operation indicator.
In case of several sequential fault lock-outs a heater lock-
out is initiated (see 4.4.2).
4.4.1.1 Malfunctions during switching-on and start
procedure
NOTE:
If malfunctions occur during switching-on or during the
start process prior to ignition, the heater will be switched
off without purge cycle.
The heater is in fault lock-out.The motor stops immedia-
tely or does not start.
Malfunction causes:
Short circuit and/or interruption of electrical
components:
burner motor (stops immediately)
Electronic ignition unit
Optional nozzle block preheater
Interruption of circulating pump operation
Flame or extraneous light detection by the flame
detector prior to ignition of the high-voltage ignition
spark.
No start: No flame detection within 15 seconds after
opening the solenoid valve.
Temperature sensor delivers unacceptable tempera-
ture values.
Heater operation outside the permissible temperature
range.
Voltage falls short of the low voltage threshold of
approx. 20.5 (10*) Volt at motor start or within a dura-
tion of 20 seconds after a heating request.
Voltage exceeding the high voltage threshold of
approx. 30 (15*) Volt at motor start or within a duration
of 6 seconds (purge cycle only, no fault lock-out).
Plug of the electronic ignition unit is inserted wrong
Control device malfunction
4.4.1.2 Malfunctions during heater operation
NOTE:
In case of malfunctions during heater operation, first a 120
seconds purge cycle will be performed. Then the heater is
switched into the fault lock-out.
Malfunction causes:
Short circuit of the circulating pump.
Short circuit or interruption of other electrical compo-
nents (motor, solenoid valve, electronic ignition unit,
nozzle block preheater).
Water temperature greater than the upper switching
threshold.
Temperature sensor delivers unacceptable tempera-
ture values.
Heater operation outside the permissible temperature
range.
Flame interruption (combustion interruption for longer
than 15 seconds).
Voltage falls short of the low voltage threshold of
approx. 20.5 (10*) Volt at motor start or within a dura-
tion of 20 seconds after a heating request.
Voltage exceeding the high voltage threshold of
approx. 30 (15*) Volt at motor start or within a duration
of 6 seconds (purge cycle only, no fault lock-out).
Control device malfunction.
4.4.1.3 Malfunctions during purge cycle
Malfunction causes:
Short circuit or interruption of the burner motor (stops
immediately)
Interruption of circulating pump operation
Heater operation outside the permissible temperature
range.
Voltage falling short of the low voltage threshold of
approx. 20.5 (10*) V at motor start or within a duration
of 20 seconds after a heating request.
Voltage exceeding the high voltage threshold of
approx. 30 (15*) V at motor start or within a duration
of 6 seconds (purge cycle is applied, but no fault lock-
out).
Control device malfunction.
* at 12V rated voltage

Related product manuals