6
Boost Charging Voltage
Sealed :14.4V/Gel14.2V/Flooded:14.6V/User:9-17V (×
2/24V)
Float Charging Voltage
Sealed/Gel/Flooded:13.8V/User:9-17V (×2/24V)
Low Voltage Reconnect Voltage
Sealed/Gel/Flooded:12.6V/User:9-17V (×2/24V)
Low Voltage / Disconnect
Voltage
Sealed/Gel/Flooded:11.1V/User:9-17V (×2/24V)
Lithium
Boost Charging Voltage
LiFePO4:14.5V/ Li-NiCoMn:12.5V / User:9-17V (×2/24V)
Low Voltage / Disconnect
Voltage
LiFePO4:12.8V / Li-NiCoMn:10.5V / User:9-17V (×2/24V)
Low Voltage / Disconnect
Voltage
LiFePO4:11.1V / Li-NiCoMn:9.3V / User:9-17V (×2/24V)
Self-consumption
≤13mA/12V;≤11.5mA/24V
Temperature compensation coefficient
-3mV//2V( Lithium battery don’t have temperature
compensation coefficient)
Communication
RS485
Working environment Tem.
-40℃~+60
Enclosure
IP68
Overall dimension
124×89×30mm
150×93.5×32.7mm
Mounting hole size
Φ3.5mm
Mounting dimension
88×76mm
120×83mm
Power cable
14AWG(2.5mm
2
)
Net weight
0.54kg
0.74kg
10. TROUBLESHOOTING
Faults
Possible reasons
Troubleshooting
LED Charging indicator
turn off during daytime
when sunshine falls on
PV modules properly
PV array
disconnection
Confirm that PV and battery wire connections are
correct and tight
No LED indicator
Battery voltage
maybe less than
8.5V
Measure battery voltage with the multi-meter.
Min.8.5V can start up the controller
Battery LED indicator
green fast Flashing
Battery over
voltage
Check if battery voltage is higher than OVD, and
disconnect the PV
Battery LED indicator
red
Battery over
discharged
When the battery voltage is restored to or above
LVR point (low voltage reconnect voltage), the load
will recover
Battery LED indicator
red flashing
Battery
Overheating
The controller will automatically turn the system
off. But while the temperature decline to be below
50 ºC, the controller will resume.
Load is not output
Load Overload
Please reduce the number of electric equipment
Restartthe controller.
wait for one night-day cycle (night time>3 hours).
Load Short Circuit
Check carefully loads connection, clear the fault.
Restartthe controller.