If a self-test error occurs, the LED will flash an Off-Red-Red-Off sequence indicating a problem. Try swapping the
IB with another IB in order to locate the problem.
If the LED is stuck in one of the 4 states, remove input power from the input terminals for a few seconds. Restore
power and check the LED for the Off-Green-Red-Yellow-Off sequence. If the LED fails to flash in the proper
sequence, replace the IB Circuit Board.
Conclusion
Should faults persist after any of the recommended remedial action above is carried out, call the local Veeder-Root
distributor or the following EMR³ technical support departments: