Setup PMC Setup
PMC Setup
Figure 3 diagrams the PMC setup programming.
Figure 3. PMC Setup
PMC SETUP
PRESS <STEP> TO CONTINUE
SETUP MODE
PRESS <FUNCTION> TO CONT
VAPOR PROCESSOR
MAX RUNTIME MINUTES: 60
Prints out a copy of the
PMC Setup entries. See
example at right.
M
P
S
S
F
TURN OFF VAPOR PROCESSOR
INCHES WC: -0.200
Range checking is enforced:
2<minutes <= 180
Default: 60 minutes
S
TURN ON VAPOR PROCESSOR
INCHES WC: +0.200
S
HYDROCARBON SELECT
PRESS <ENTER>
Use <ENTER> key to make selection
MODBUS Sensor default enabled
S
OVER PRESSURE LIMIT
INCHES WC: xx.xx
Range checking is enforced:
0 < xx.xx < 3.5
Default: 0.0
S
DUTY CYCLE LIMIT
xx.xx %
Range checking is enforced:
0 < xx.xx < 100
Default: 75%
Use <CHANGE> key to enter.
Default Start time = 11:59 PM
Use <CHANGE> key to enter.
0< delay < =720
Default:= 001
NOTE: If delay minutes =0, the results will be posted as soon as
they become available, else mmm minutes after start time.
Data collected 5 minutes before the Start of Test time is omitted
from test.
S
SET ANALYSIS TIME
PRESS <ENTER>
E
S
SET TEST START TIME
TIME: hh:mm
SET POST DELAY DURATION
DELAY MINUTES: mmm
isd\pmc-1.eps
C
F
P
S
T
Change
E Enter
Function
Print
M Mode
Step
Tank/Sensor
Key press
sequence
Repress until
desired message
appears in display
Key Legend
1
2
PMC SETUP
----------------------
PMC VERSION: 01.00
VAPOR PROCESSOR TYPE
VST VAPOR PROCESSOR
MAX RUNTIME MINUTES: 90
ON: -0.200 INCHES
OFF:-0.600 INCHES
EFFLUENT EMISSIONS LIMIT
0.649 LB/1KG
OVER PRESSURE LIMIT
xx.xx PERCENT%
DUTY CYCLE LIMIT
xx.xx PRECENT%
ANALYSIS TIMES
TIME 11:59 PM
DELAY MINUTES 1
+3
0
+0.2
Turn On
vapor processor
Ullage vapor pressure
Turn Off
vapor processor
-0.2
-8
Absolute
Range
(IWC)
P/V valve opens
Vapor Processor
On/Off example
Sets vapor processor Off point. Range:
-8 < Off setting < On setting. For more
information see example at right.
Sets vapor processor On point. Range:
Off setting < On setting < +3. For more
information see example at right.
NOTE: This menu is not used.
Section 16
Pressure Management Control
16-6

Other manuals for Veeder-Root TLS-350 PLUS