18
VEGAMET 841, 842, 861, 862 • Installation in Zone 2
61274-01-191219
Intrinsically safe circuit
Supplyandsignalcircuit:
4 … 20 mA-Sensor 1: Terminals 1[+], 2[-]
In addition only VEGAMET 862:
4 … 20 mA sensor 2: Terminals 4[+], 5[-]
In type of protection intrinsic safety Ex ia IIC, IIB/IIIC.
For connection to a certied, intrinsically safe circuit.
U
o
≤ 23.3 V DC
I
o
≤ 111.3 mA
P
o
≤ 648.4 mW
Characteristics: linear
C
i
negligibly small
L
i
negligibly small
The maximum values given in the table can be used as concentra-
ted capacitances and concentrated inductances.
The values for IIC and IIB are also permissible for dust explosi-
ve areas.
Ex ia IIC IIB, IIIC IIA
Permissible external inductance L
o
0.2 mH 0.5 mH 0.5 mH 2 mH 10 mH
Permissible external capacitance C
o
120 nF 88 nF 580 nF 470 nF 760 nF
The intrinsically safe circuits of VEGAMET 841, 842, 861, 862 are galvanically separated from
ground.
The intrinsically safe circuits of the VEGAMET 841, 842, 861, 862 are reliably separated from the
non-intrinsically safe circuit up to a peak value of 375 V.
The maximum voltage on the non-intrinsically safe circuits must not exceed 253 Vrms in the event of
a fault.
10 Mechanical data
The following mechanical data are valid for all housing and electronics versions.
Mechanical data
Protection (IEC/EN 60529) TYPE 4X, IP66/IP67
Connection cross-section:
0.25 … 2.5 mm
2
Overvoltage category II
Pollution degree 4
11 Thermal data
Permissibleambienttemperatures
Permissible ambient temperature at the installation lo-
cation of an instrument
Ambienttemperature(Ta)
as associated apparatus for installation in zone 2 -40 … +50 °C (-40 … +122 °F)
12 Installation
The controllers VEGAMET 841, 842, 861, 862 as associated equipment for installation in zone 2