15 Supplement
VEGAMET 862 • 4 … 20 mA/HART
58867-EN-200401
15 Supplement
15.1 Technical data
Note for approved instruments
The technical data in the respective safety instructions are valid for approved instruments (e.g. with
Exapproval).Insomecases,thesedatacandierfromthedatalistedherein.
All approval documents can be downloaded from our homepage.
Materials and weights
Materials
Ʋ Housing PC-FR
Ʋ Housing screws StSt
Ʋ Inspection window PE
Ʋ Seal Silicone
Ʋ Cable glands PA
Ʋ Sun shade 316L
Ʋ Brackets for tube mounting V2A
Weight with mounting plate 1310 g (2.888 lbs)
Voltage supply
Operating voltage
Ʋ Nominal voltage AC 100 … 230 V (-15 %, +10 %) 50/60 Hz
Ʋ Nominal voltage DC 24 … 65 V DC (-15 %, +10 %)
Power consumption max. 19 VA; 7 W
Sensor input
Number of sensors 2 x 4 … 20 mA/HART
Type of input (selectable)
Ʋ Active input Sensor supply through VEGAMET 862
Ʋ Passive input Sensor has an own voltage supply
Measured value transmission
Ʋ 4 … 20 mA analogue for 4 … 20 mA sensors
Ʋ HART protocol digital for HART sensors
Deviation (4 … 20 mA)
Ʋ Accuracy ±20 µA (0.1 % of 20 mA)
Terminal voltage 27 … 22 V at 4 … 20 mA
Current limitation approx. 26 mA
Detection line break ≤3.6mA
Detection shortcircuit ≥21mA
Adjustment range 4 … 20 mA sensor
Ʋ Empty adjustment 2.4 … 21.6 mA
Ʋ Full adjustment 2.4 … 21.6 mA