2a. Connect the Lock (Dry)
When using an external power supply which uses a dry contact, ensure that
“NONE” is selected on the door power selection switch.
Fail Secure
Fail Safe
2b. Connect the Lock (Wet)
In a Wet configuration, ensure that power selection
for each door is set to the correct voltage as
outlined by the locking hardware specifications.
Set it to “12VDC” for 12 volt locking hardware
Set it to “24VDC” for 24 volt locking hardware
The AC42 is rated to power 12V locks up to 1A and
24V locks up to 500mA.
Fail Safe
LOCK (+) positive goes into NC
LOCK (-) negative and ground wire goes into COM
Fail Secure
LOCK (+) positive goes into NO
LOCK (-) negative and ground wire goes into COM
Installation
Connecting a Door 2/5
When connecting the lock in the WET
configuration, ensure the negative of
the lock goes into the COM port as
shown in the diagrams below.